Selection Of Wiring Equipment - Toshiba TOSVERT VF-AS1 Instruction Manual

The new high-performance inverter tosvert
Hide thumbs Also See for TOSVERT VF-AS1:
Table of Contents

Advertisement

Selection of wiring equipment

Voltage
Applicable
class
motor [kW]
0.4
0.75
1.5
2.2
3.7/4.0
5.5
7.5
11
200V
class
15
18.5
22
30
37
45
55
75
0.75
1.5
2.2
3.7/4.0
5.5
7.5
11
15
18.5
22
30
37
400V
45
class
55
75
10
90
110
132
160
200
220
280
355
400
500
(*1): Type forms of Toshiba Schneider Electric Ltd. products.
(*2): Selections for use of the Toshiba 4-pole standard motor with power supply voltage of 200V/400V-50Hz.
(*3): Choose the MCCB according to the power supply capacity.
For comply with UL and CSA standard, use the fuse certified by UL and CSA.
(*4): When using on the motor side during commercial-power supply operation, choose the MC with class AC-3 rated current for
the motor rated current.
(*5): Attach surge killers to the magnetic contactor and exciting coil of the relay.
(*6): In the case the magnetic contactor (MC) with 2a-type auxiliary contacts is used for the control circuit, raise the reliability of
the contact by using 2a-type contacts in parallel connection.
Input current[A]
Inverter model
Without
Reactor
VFAS1-2004PL
3.5
VFAS1-2007PL
6.1
VFAS1-2015PL
11.5
VFAS1-2022PL
15
VFAS1-2037PL
26.0
VFAS1-2055PL
35
VFAS1-2075PL
45
VFAS1-2110PM
-
VFAS1-2150PM
-
VFAS1-2185PM
-
VFAS1-2220PM
-
VFAS1-2300PM
-
VFAS1-2370PM
-
VFAS1-2450PM
-
VFAS1-2550P
-
VFAS1-2750P
-
VFAS1-4007PL
3.7
VFAS1-4015PL
5.8
VFAS1-4022PL
8.2
VFAS1-4037PL
14.0
VFAS1-4055PL
20.5
VFAS1-4075PL
27
VFAS1-4110PL
36.5
VFAS1-4150PL
48
VFAS1-4185PL
-
VFAS1-4220PL
-
VFAS1-4300PL
-
VFAS1-4370PL
-
VFAS1-4450PL
-
VFAS1-4550PL
-
VFAS1-4750PL
-
VFAS1-4900PC
-
VFAS1-4110KPC
-
VFAS1-4132KPC
-
VFAS1-4160KPC
-
VFAS1-4200KPC
-
VFAS1-4220KPC
-
VFAS1-4280KPC
-
VFAS1-4355KPC
VFAS1-4400KPC
VFAS1-4500KPC
No-fuse breaker (MCCB)
Without Reactor
Rated
Type
With
current
form
Reactor
[A]
(*1)
2.1
6.3
GV2 L10
3.2
10
GV2 L14
6.4
18
GV2 L20
9.3
25
GV2 L22
15.5
32
GV2 L32
22. 5
50
NJ50EB
34.5
60
NJ100FB
53.5
-
-
72
-
-
77
-
-
88
-
-
125
-
-
140
-
-
165
-
-
200
-
-
270
-
-
2.1
5
GV2 L10
3.8
10
GV2 L14
5.7
14
GV2 L16
8.7
18
GV2 L20
12.7
32
GV2 L32
16.3
32
GV2 L32
21.5
50
NJ50EB
33.5
60
NJ100FB
45.5
-
-
50
-
-
66
-
-
84
-
-
105
-
-
120
-
-
165
-
-
170
-
-
200
-
-
240
-
-
290
-
-
360
-
-
395
-
-
495
-
-
J-2
E6581300
Magnetic contactor
(MC)
Without
With Reactor
Reactor
Rated
Type
Type
current
form
form
[A]
(*1)
(*1)
4
GV2 L08
LC1D096
6.3
GV2 L10
LC1D096
10
GV2 L14
LC1D096
14
GV2 L16
LC1D096
25
GV2 L22
LC1D126
32
GV2 L32
LC1D126
40
NJ50EB
LC1D326
75
NJ100FB
-
100
NJ100FB
-
100
NJ100FB
-
125
NJ225FB
-
150
NJ225FB
-
175
NJ225FB
-
200
NJ225FB
-
250
NJ400F
-
350
NJ400F
-
4
GV2 L08
LC1D096
6.3
GV2 L10
LC1D096
10
GV2 L14
LC1D096
14
GV2 L16
LC1D096
25
GV2 L22
LC1D126
25
GV2 L22
LC1D186
30
NJ30E
LC1D256
40
NJ50EB
LC1D326
60
NJ100FB
-
60
NJ100FB
-
100
NJ100FB
-
100
NJ100FB
-
125
NJ225FB
-
150
NJ225FB
-
200
NJ225FB
-
200
NJ225FB
-
250
NJ400F
-
300
NJ400F
-
350
NJ400F
-
500
NJ600F
-
500
NJ600F
-
600
NJ600F
-
With
Reactor
Type
form
(*1)
LC1D096
LC1D096
LC1D096
LC1D096
LC1D096
LC1D126
LC1D256
LC1D506
LC1D506
LC1D506
LC1D806
LC1D806
LC1D115J
LC1D150J
LC1F185J
LC1F265J
LC1D096
LC1D096
LC1D096
LC1D096
LC1D126
LC1D186
LC1D186
LC1D256
LC1D326
LC1D326
LC1D506
LC1D806
LC1D806
LC1D806
LC1D115J
LC1D150J
LC1D185J
LC1D225J
LC1D265J
LC1D400J
LC1D400J
LC1D500J