All 200V VF-AS1 and 400V VF-AS1 with ratings of up to 160kW have built-in dynamic braking resistors as standard
equipment. If the rating of your inverter falls within this range, connect the resistor, as shown in Figure a) below or
Figure b) on the next page. If your inverter has a power rating of 200kW or more, connect a resistor, as shown in
Figure c).
Connecting an external braking resistor (optional)
a) External braking resistor (with a thermal fuse) (optional)
Three-phase
main circuit
Power supply
5
[Parameter setting]
Title
Do not connect an external resistor with a resistance (combined resistance) smaller than the minimum admissible
resistance.
For overload protection, be sure to set the parameters
[Parameter setting]
Title
MCCB
PA/+
R/L1
S/L2
T/L3
Function
Dynamic braking selection
Function
Dynamic braking resistance
Allowable continuous braking
resistance
Braking resistance overload
time
An external braking resistor
(optional)
PB
U
V
W
Inverter
Adjustment range
:Deselect
:Select (bracking resistance
overload detect)
: Select (bracking resistance
overload not detect)
and
properly.
Adjustment range
~
~
kW
~
sec.
E-36
E6581301
Motor
IM
Example of setting
Example of setting
Any value
Any value
Set the parameter to
for type PBR*- or to
any value for other
types.