Toshiba TOSVERT VF-AS1 Instruction Manual page 50

The new high-performance inverter tosvert
Hide thumbs Also See for TOSVERT VF-AS1:
Table of Contents

Advertisement

Terminal
Input/
symbol
output
PP
Output
Analog input setting power output
SW3: Multifunction programmable analog input
terminal when SW3 is in the RR position.
RR/S4
Input
Standard default setting:0~10Vdc input and
0~60Hz frequency.
Multifunction programmable analog input.
Standard default setting: 0~10Vdc input and
0~60Hz frequency.
VI/I I
Input
2
This terminal can also be used as a 4-20mAdc
(0-20mAdc) input terminal, if the parameter
Multifunction programmable analog input.
RX
Input
Standard default setting:0~±10Vdc input and
0~±60Hz frequency.
Multifunction programmable analog output.
Standard default setting: output frequency
Use this terminal to connect a 1mAdc full-scale
FM
Output
ammeter. This terminal can also be used as a 0-
10V (
(
10V/0-20mA side.
Multifunction programmable analog output.
Standard default setting: output current
AM
Output
Use this terminal to connect a 1mAdc full-scale
ammeter or 7.5Vdc (10Vdc)-1mA full-scale
voltmeter.
Multifunction programmable open collector
output. The default setting is to output a signal
when output low speed threshold has been
OUT1
reached. Depending on the SW4 setting,
pulses are output with frequencies of 1.00kHz
to 43.20kHz. Standard default setting:3.84kHz
Output
Multifunction programmable open collector
output. By default, it is set to output a signal
OUT2
indicating the completion of acceleration or
deceleration.
Digital output signal equipotential (0V) terminal
NO
for the control circuit. It is isolated from the CC
terminal.
Common
CCA
Analog input/output signal equipotential (0V)
to input/
*1
terminal for the control circuit.
output
DC power input terminal for operating the
+SU
Input
control circuit. Connect a control power backup
device (optional) between +SU and CC.
Relay contact output. Contact rating
FLA
Used to detect the activation of the inverter's
FLB
Output
protective function. Contact across FLA-FLC is
FLC
closed and FLB-FLC is opened during
protection function operation.
*1: Although the CC terminal and the CCA terminal are not insulated, they should be used separately, one for the logic circuit and
the other for the analog circuit.
Function
set to
.
= ) or 0-20mA terminal
= ), if the SW2 switch is set to 0-
Electrical
specifications
10Vdc
(Permissible load
current:10mAdc)
10Vdc
(Internal impedance:30 kΩ)
10Vdc
(Internal impedance:30 kΩ)
4~20mA
(Internal impedance:242Ω)
10Vdc
(Internal impedance:22 kΩ)
1mA full-scale DC
ammeter
0-10V
0-20mA (4-20mA)
Full-scale DC
ammeter
1mA full-scale DC
ammeter or 7.5Vdc-
1mA full-scale DC
voltmeter
Open collector output
24Vdc-50mA
*Sink logic/source
logic switchable
-
Voltage:24Vdc±10%
Use a power supply
with a current rating of
1.1A or more.
250Vac-2A
30Vdc-1A
:at resistance load
250Vac-1A
:cos
=0.4
ƒ Ó
B-10
E6581301
Inverter internal circuits
15V
Constant
voltage
circuit
P5
S4
2.2k
12.7k
RR
15k
SW3
P5
15k
242
15k
P15
15k
7k
120
0-1mA
SW2
+
-
+
-
0-10V
70
4.7k
0-20mA
4.7k
+
-
P24
OUT1
SW4
PULS
LO
OUT2
20
20
NO
-
P24
1
+SU
CC
P24
FLA
FL
FLB
FLC

Advertisement

Table of Contents
loading

Table of Contents