6.35.2 Setting of optional meter outputs

⇒ For details, refer to Instruction Manual (E6581341) specified in Section 6.41.

6.35.3 Calibration of analog outputs

•Function
Output signals from FM/AM terminals are analog voltage signals. Their standard setting range is from 0 to
10Vdc.
The output current from terminal FM can be changed to 0 to 20mAdc (or 4 to 20mAdc) by changing the settings
of terminal SW2 and a parameter.
[Parameter setting]
6
Note: To switch to 0-20mAdc (4-20mAdc), set
FM terminals setting example
SW2=OFF
SW2=OFF
The analog output inclination can be adjusted using the parameter
For code data 50 to 64, negative inclination is invalid.
~
,
: FM voltage/current output switching
,
: FM output gradient characteristic and bias adjustment
,
: AM output gradient characteristic and bias adjustment
Title
Function
FM voltage/current output
switching
FM output gradient
characteristic
FM bias adjustment
AM output gradient
characteristic
AM bias adjustment
,
=
(mA)
20
0
0
100%
Internal calculated value
=
=
(mA)
20
: Large gain
0
0
100%
Internal calculated value
~
: Meter output settings
Adjustment range
: Voltage 0~10V output
: Current 0~20mA output
: Negative gradient
(descending)
: Positive gradient (ascending)
-
. %
: Negative gradient
(descending)
: Positive gradient (ascending)
-
. %
to
.
=
(%)
SW2=OFF
=
(%)
SW2=OFF
F-66
E6581301
Default setting
,
=
=
(mA)
20
4
0
100%
Internal calculated value
=
=
=
(mA)
20
:Small gain
4
0
100%
Internal calculated value
(%)
(%)