Technical information described in this document is used to explain typical operations and applications of products, and this is not intended to grant warranty or licensing right on its use regarding TOSHIBA group or a third party intellectual property and other right. E 6 5 8 1 3 6 4 ②...
1.1.1. Switching circuit connection diagram, Time chart, Parameter settings Inverter protective action signal (Inverter) (Commercial power) Title Output signal selection of commercial power/inverter switching Inverter side switching waiting time Commercial power side switching waiting time ...
G / E OUT2 OUT1 CCA RX VI/II RR/S4 PP *7: VF-AS1's 'WP1/WN1' model and VF-PS1 don't have 'ST' terminal. Please set next parameter for use 'S3' terminal as 'ST' function. f110 (Always ON function selection 1) f117 (Input terminal function selection: S3) = 6...
1.2.1. Switching circuit connection diagram, Time chart, Parameter settings Inverter protective action signal (Inverter) (Commercial power) Y-△Switching timer Setting frequency P24-OUT1(RY1) for inverter run output P24-OUT2(RY2) for commercial power run output Run signal F-CC Stand-by signal ST-CC Reset signal RES-CC E 6 5 8 1 3 6 4 Inverter trip occurs...
Title Output signal selection of commercial power/inverter switching Inverter side switching waiting time Commercial power side switching waiting time Input terminal selection #6 (S2) Output terminal selection #1 (OUT1) Output terminal selection #2 (OUT2) *1:Be careful about Items 5 and 7 in 1.3, “Precautions.”...
2.1.1. Switching circuit connection diagram, Time chart, Parameter settings Inverter protective action signal (Commercial (Inverter) power) RY1(Inverter) RY2(Commercial power) Title Output signal selection of commercial power/inverter switching Commercial power/inverter switching frequency Inverter side switching waiting time Commercial power side switching waiting ...
2.2. Precautions 1. Make sure to interlock the magnetic contactor (MC3) on the inverter output side with the commercial power supply magnetic contactor (MC1). 2. Magnetic contactor (MC2) can be omitted for normal operation but this is needed to isolate the inverter circuit in case a short-circuit fault occurs inside the inverter.