Setup By Analog Input Signals (Rr/S4 Terminal) - Toshiba TOSVERT VF-AS1 Instruction Manual

The new high-performance inverter tosvert
Hide thumbs Also See for TOSVERT VF-AS1:
Table of Contents

Advertisement

7.3.1 Setup by analog input signals (RR/S4 terminal)

If a potentiometer (1~10kΩ-1/4W) for setting up frequency is connected with the RR/S4 terminal, the inverter can be
run and stopped with external commands.
For bringing this function into practice, connect a potentiometer to the terminals of PP, RR/S4 and CC so as to divide
the reference voltage (10Vdc) at the terminal PP and to input 0 to 10Vdc of divided voltage between the RR/S4 and CC
terminals.
If analog voltage signal of 0 to 10Vdc is input between the terminals of RR/S4 and CC, frequency can be set up without
connection of a potentiometer.
Title
Command mode selection
Frequency setting mode selection 1
FM terminal meter selection
FM terminal meter adjustment
Frequency priority selection
Analog input filter
RR/S4 input point 1 setting
RR/S4 input point 1 frequency
RR/S4 input point 2 setting
RR/S4 input point 2 frequency
*1: Inverter with a model number ending with -WN: 60.0 -WP: 50.0
MCCB
Power
supply
Function
-
filter)
CHARGE
U/T1
R/L1
VF-AS1
V/T2
S/L2
W/T3
T/L3
RES
S1
S2
FLA
S3
FLB
FLC
ST
F
P24/PLC
R
OUT1
OUT2
FM
AM
NO
CC
CC
CCA RX
VI/II
RR/S4
PP
1~10kƒ ¶ -1/4W
G-11
Adjustment range
Default setting
~
(Terminal)
~
(RR/S4)
~
-
,
(No filter)~
(Max.
~
%
~
Hz
~
%
~
Hz
*1
■Run/stop setup
To control switching between forward run
Motor
(F) and reverse run (R), and stop by
external commands.
IM
• ¡ Setup of frequency setting signal and
running frequency characteristic
To set up frequency setting signal to be
input to the potentiometer (RR/S4
terminal) and characteristic of running
frequency.
Frequency characteristic is set up at the
two points of RR/S4 reference point 1
(
)/frequency (
reference point 2 (
(
).
Connection and calibration of
• ¡
Forward run
frequency meter
Connect a 1mAdc full-scale DC current
Reverse run
meter, 7.5Vdc full-scale DC voltmeter or
rectifier type AC voltmeter. For
calibration of the meter, refer to the
Section 5.16.
Frequency
Hz
meter
Point 1
Operation
frequency
0%       100%
(0V    ~  
E6581301
Example of setting
(Terminal)
(RR/S4)
-
*1
), RR/S4
)/frequency
Point 2
%
10V)
Frequency setting
7