Toshiba TOSVERT VF-AS1 Instruction Manual page 191

The new high-performance inverter tosvert
Hide thumbs Also See for TOSVERT VF-AS1:
Table of Contents

Advertisement

<Broadcast>
When an operation frequency command is broadcasted from the host computer to inverters
Host computer
INV
INV
No.00
No.01
: Use the terminal board to branch the cable.
(1) Data is sent from the host computer.
(2) Data from the computer is received at each inverter and the inverter numbers are checked.
(3) Data with an asterisk (*) in the inverter number position is taken as broadcast data and the command is
deciphered and executed.
(4) To avoid collisions between data, only the inverter with the asterisk (*) replaced with a zero (0) returns data to
the host computer.
(5) As a result, all inverters connected are operated at the operation frequency specified by the command
broadcasted.
Note: If an inverter number is assigned to each group of inverters, data can be broadcasted on a group-by-group
basis.
(This function is usable only in ASCII mode. For binary mode, see Instruction Manual (E6581315)
specified in Section 6.41.)
Ex.) When the inverter number *1 is specified, data is broadcasted to inverters Nos. 01, 11, 21, 31, ... 91.
At that time, data is returned by the inverter bearing number 01.
Inverter-to-inverter communication
When all slave inverters are connected they operat at the same frequency as the master inverter (no setting of point
frequencies in this case)
Master inverter
INV
INV
No.00
No.01
: Use the terminal board to branch the cable.
(1) The master inverter transmits frequency command data to its slave inverters.
(2) The slave inverter calculate a frequency reference from the data received and save the frequency calculated.
(3) As a result, all slave inverters operate at the same frequency as the master inverter.
Note: The master inverter always sends frequency command data to its slave inverters.
The slave inverters are always on standby so that they can receive an frequency command from the master
inverter at anytime.
Setting for issuing run/stop commands from an external control device
Title
Function
Command mode selection
Note:When parameter
cannot be used for slave inverters.
Setting for issuing speed commands from an external control device
Title
Function
Frequency setting mode
selection 1
INV
INV
No.02
No.03
INV
INV
No.02
No.03
Adjustment range
~
(setting for communications between inverters) is used, the setting
Adjustment range
~
F-79
: Wiring
: Data (host → INV)
INV
INV
No.29
No.30
: Wiring
: Data (Master → Slave)
INV
INV
No.29
No.30
Default setting
Example of setting
(Terminal input enabled)
Default setting
Example of setting
(RR/S4 input)
E6581301
6
(4-wire RS485)
=
(4-wire RS485)

Advertisement

Table of Contents
loading