Communication parameters (4-wire RS485)
These parameters allow you to change the communication speed, parity, inverter number, communication error trip
timer setting, etc. from the operation panel or an external control device.
Title
6
Function
Parity
(common to 2-wire RS485 and 4-wire RS485)
Inverter number (common)
Communications time-out time
(common to 2-wire RS485 and 4-wire RS485)
Communications time-out action *
(common to 2-wire RS485 and 4-wire RS485)
Frequency point selection
Point 1 setting
Point 1 frequency
Point 2 setting
Point 2 frequency
Communication speed (4-wire RS485)
Send waiting time (4-wire RS485)
Inverter-to-inverter communication setting
(4-wire RS485)
Protocol selection (4-wire RS485)
Block write data 1
Block write data 2
Adjustment range
:Non parity
:Even parity
:Odd parity
~
:OFF
~
sec.
2-wire
Setting
RS485
No action
Alarm
Trip
No action
Alarm
Trip
No action
Alarm
Trip
:Disabled
:2-wire RS485
:4-wire RS485
:Communication add option
~
%
~
Hz
~
%
~
Hz
:9600 bps,
:19200 bps,
:38400 bps
:Default,
:Slave (issues a 0Hz command if
something goes wrong with the
master)
:Slave (continues operation if
something goes wrong with the
master)
:Slave (trips for emergency stop if
something goes wrong with the
master)
:Master (sends a frequency
command)
:Master (sends an output frequency)
:Master (sends a torque command)
:Master (sends an output torque
command)
:TOSHIBA
:MODBUS
:Deselect
:Command information 1
:Command information 2
:Frequency command
:Terminal board output data
:Communication analog output
Ditto
F-80
E6581301
Default setting
4-wire
RS485
No action
No action
No action
Alarm
Alarm
Alarm
Trip
Trip
Trip
Inverter with a
model number
ending with
-WN:
-WP:
~
sec.