Method of resetting causes of trip

Do not reset the inverter when tripped because of a failure or error before eliminating the cause. Resetting the tripped
inverter before eliminating the problem causes it to trip again.
For recovering inverter from trip status,
(1) By turning off the power (Keep the inverter off until the LED turns off.)
⇒ Refer to Section 6.33.2 (inverter trip retention selection
(2) By means of an external signal (shorting RES and CC on control terminal board → release)
(3) By operation panel operation
(4) By means of a communication
⇒ For details, refer to the instruction manual for the communications device used
reset it in one of the following ways.
To reset the inverter by operation panel operation, follow these steps.
1. Check whether the LED on the control panel indicates that tripping has occurred. If the occurrence of tripping is
not indicated, press the MODE key to display it.
2. Press the STOP key and make sure that
3. Pressing the STOP key again will reset the inverter if the cause of the trip has already been eliminated.
When any overload function [
active, the inverter cannot be reset by inputting a reset signal from an external device or by operation panel
operation before the virtual cooling time has passed.
Standard virtual cooling time ... In case of
13
Note:
note that the inverter is in a state easy to trip during virtual cooling time.
If the inverter trips because of overheat (
completely, because overheat is detected based on its internal temperature.
- Caution -
For quickly recovering inverter from trip status, turn it off once and reset it. However, this measure is taken
frequently, it may cause damage to the motor and other component units.
Description
Overcurrent pre-alarm
Same as
Overvoltage pre-alarm
Same as
Achieving PBR operation
blink while PBR is operating is not an
level
error.
Overload pre-alarm
Same as
Overheat pre-alarm
Same as
Communication error
•Various transmission errors occur
when computer is linked up with
inverter system.
•Various transmission errors occur in
inverter to inverter communication
(slave side). Time-out or trip in master
side.
,
,
, ......,
,
,
,
,
are displayed in this order from left to right.
specified in section 6.41.
: Inverter overload,
In case of
In case of
or
can be reset during virtual cooling time if the CPU1 version is Ver.106 or successor. However,
Possible causes
(Overcurrent)
(Overvoltage)
and
(Overload)
(Overheat)
) for details.
is displayed.
: Motor overload,
: for about 30 seconds after trip
: for about 120 seconds after trip
: for about 20 seconds after trip
), reset it after a considerably long time enough for cooling it down
M-6
E6581301
Remedies
Same as
(Overcurrent)
Same as
(Overvoltage)
blink while PBR is operating is not an
error.
Same as
and
(Overload)
Same as
(Overheat)
•For measures to correct various kinds
of data transmission errors, refer to
the instruction manual for the
communications device used specified
in Section 6.41.
•Check the master inverter.