1. Basic parameter [3/4]
Communi
Title
cation
Function
No.
Motor overload protection
0600
level 1
Motor overload protection
0017
characteristic selection
Current/voltage unit
0701
selection
FM terminal meter
0005
selection
FM terminal meter
0006
adjustment
AM terminal meter
0670
selection
AM terminal meter
0671
adjustment
0300
PWM carrier frequency
Auto-restart control
0301
selection
Regenerative power ride-
0302
through control
Dynamic braking
0304
selection
Dynamic braking
0308
resistance
Allowable continuous
0309
braking resistance
*1: ⇒ For the adjustment range, see the table on page K-39.
*3: Default values vary depending on the capacity. ⇒ See the table of K-46.
Adjustment range
10~100%
Overload
Setting Motor type
protection
0
○ (protect)
× (not stall)
1
Standard
○ (protect)
○ (stall)
Motor
2
× (not protect)
× (not stall)
3
× (not protect)
○ (stall)
4
○ (protect)
× (not stall)
5
○ (protect)
○ (stall)
VF Motor
6
× (not protect)
× (not stall)
7
× (not protect)
○ (stall)
0:%, 1:A (ampere)/V (volt)
0~64 *1
-
0~64 *1
-
1.0~16.0kHz (1.0~8.0kHz) *2
0:Deselect
1:At auto-restart
2:ST ON/OFF switching
3:1+2
4:Starting
0:Deselect
1:Power ride-through
2:Deceleration stop during power failure
3:Synchronized deceleration/acceleration (synchronized
acceleration/deceleration signal)
4:Synchronized deceleration/acceleration (synchronized
acceleration/deceleration signal+power failure)
0:Deselect
1:Select (braking resistance overload detect)
2:Select (braking resistance overload not detect)
0.5~1000Ω
0.01~600.0kW
*2: For 200V-55/75kW models and 400V-90kW to 400V-280kW models, the carrier frequency is between 1.0 and 8.0kHz inclusive.
Sensorless vector/vector with sensor (●:Effective, -:Ineffective)
Minimum
setting unit
Default
Write during
(Panel/Communi
setting
running
cation)
1/1
100
Enabled
OL stall
1/1
0
Enabled
1/1
0
Enabled
1/1
0
Enabled
1/1
-
Enabled
1/1
2
Enabled
1/1
-
Enabled
0.1/0.1
*3
Enabled
1/1
0
Disabled
1/1
0
Disabled
1/1
0
Disabled
0.1/0.1
*3
Disabled
0.01/0.01
*3
Disabled
Vector control
PM
Speed
Torque
V/f
Reference
control
control
control
●/●
●/●
●/●
5. 14
●/●
●/●
●/●
●/●
●/●
●/●
●/●
●/●
●/●
●/●
●/●
●/●
●/●
●/●
5. 18.1
●/●
-/-
5. 18. 2
●/●
●/●
●/●
●/●
●/●
●/●
5. 14
5. 14
5. 15
5. 16
5. 16
5. 16
5. 16
5. 17
5. 19
5. 19
5. 19