9. Selection of peripheral devices
・ When using the inverter without the front cover, be sure to place the inverter unit inside a
cabinet. If they are used outside the cabinet, it may cause electric shock.
Mandatory
・Be sure to ground every unit. If not, it may cause electric shock or fire on the occasion of
failure, short-circuit or electric leak.
Be grounded

9. 1 Selection of wiring equipment

Applicable
Voltage
motor
class
[kW]
18.5
22
30
37
200V
45
class
55
75
90
110
18.5
22
30
37
45
55
75
90
400V
110
class
132
160
200
220
280
315
(*1): Indicates wire sizes of input terminals R, S, T and output terminals U, V, W. Wiring distance is supposed to
be 30 m at maximum.
(*2): Cable sizes in this table is in case of 75 degree copper wire.
(*3): For the control circuit, use shielded wires whose size (cross-section) is 0.75 mm
(*4): For the earth cable, use wires larger than the specified ones in size (cross-section).
(*5): Do not connect more than two wires to a terminal block (except for terminal blocks of 2900, 2110K, 4160K
to 4315K and PA terminals of models that have only one PA terminal). If wiring with more than two wires is
needed, set a external relay terminal.
  Danger
  
Inverter model
Main circuit(*1)
VFP7-2185P
4(22)
VFP7-2220P
2(38)
VFP7-2300P
2/0(60)
VFP7-2370P
VFP7-2450P
4/0(100)
VFP7-2550P
VFP7-2750P
300(150)
VFP7-2900P
VFP7-2110KP
400(200)
VFP7-4185P
8(8)
VFP7-4220P
6(14)
VFP7-4300P
VFP7-4370P
4(22)
VFP7-4450P
2(38)
VFP7-4550P
VFP7-4750P
VFP7-4900P
4/0(100)
VFP7-4110KP
VFP7-4132KP
VFP7-4160KP
300(150)
VFP7-4200KP
400(200)
VFP7-4220KP
VFP7-4280KP
300×2
VFP7-4315KP
(150×2)
I-1
Wire size   AWG(cross-section[mm
Braking resistor/
DC reactor
(optional)
2(38)
2/0(60)
4/0(100)
300(150)
400(200)
300×2
(150×2)
6(14)
4(22)
2(38)
2/0(60)
4/0(100)
300(150)
400
(100×2)
300×2
(150×2)
400×2
(200×2)
2
])
Braking
Earth cable
unit(optional)
8(8)
4(22)
6(14)
2(38)
2/0(60)
2(38)
4/0(100)
8(8)
10(5.5)
6(14)
4(22)
6(14)
4(22)
2/0(60)
2(38)
4/0(100)
4/0(100) or
2×2(38×2)
4/0(100) or
300
2/0(60×2)
(150)
2
or more.