Table 7‑2. Inverter replacement parts
Door seal gaskets
Battery (CR1216)
Air filters
Card cage filter
CHECKING AND REPLACING THE AIR
FILTERS
As part of preventative maintenance, every 12 months you should perform regular
checks of the self-contained cooling system to determine if the air filters need to be
replaced. Cleaning may be required more often depending on the location of the
inverter or the air filters might need to be replaced.
Maintaining the Air Filters
TOOLS REQUIRED
• Flat-head screwdriver
• 5/32" Allen wrench
TO MAINTAIN THE AIR FILTERS
The air intake hoods are mounted on gas shocks. The hoods must be in the open
position to clean the filters.
1. Shutdown the inverter prior to starting this procedure and wait five minutes.
2. Using a flat-head screwdriver, turn each of the six retainer tabs a three-quarter
turn. The air intake hoods can now be lifted to the open position.
7‑4
Part
Maintenance
Replacement Schedule
5 years
When a Real Time Clock error occurs in
Modbus PVM status register 42005.
As needed
As needed