The bottom chases are located beneath the bottom DC and AC gland plates. If the
bottom side chase is used, the bottom DC and AC gland plates are not needed and
can be removed from the cabinet. The gland plates should not be left loose in the
compartment.
 Important
The gland plate on the front of the inverter, next to the DC combiner sub panel
door, is intended for service access only and should not be used for conductor
entry.
TOOLS REQUIRED
• 5/32" hex wrench
• NEMA 4 conduit hubs
• Knockout punch
TO USE THE GLAND PLATES
 Important
All penetrations in the inverter cabinet must be through the gland plates which
are provided for the sole purpose of a safe and convenient way to route wiring
in to and out of the inverter. Penetrating the inverter cabinet in any other
location besides the gland plates voids the warranty.
 Important
Remove all metal shavings and wire scraps from the inverter prior to replacing
the gland plates.
1. Select the size(s) and location(s) of the hole(s) that need to be punched.
Figure 4‑12. DC bottom entry gland plates
570-1001791-05A
Advanced Energy® AE 500 Inverter
DC bottom entry gland plate
4686
Installing