AC/DC DISCONNECT DEVICE AND OTHER REQUIREMENTS
If the optional inverter integrated AC disconnect and inverter integrated DC
subcombiner breakers were not selected, then isolated disconnect devices must be
provided for both the PV array DC connection and for the AC utility grid connection
when installing an AE inverter.
AC DISCONNECT DEVICE, OVERCURRENT PROTECTION,
AND TRANSFORMER REQUIREMENTS
If the optional inverter integrated AC disconnect was not selected, then you must
install an AC disconnect and overcurrent protection device at the AE inverter that
complies with National Electric Code ANSI/NFPA 70 and local building code
requirements, whichever is more restrictive. The AC disconnect must be rated for
480 VAC at the maximum overcurrent protection setting, typically 1.25 * IAC
maximum. You must connect the inverter to a three-phase 480 VAC grounded wye
feeder or an 800 A service. Refer to the table below.
DC DISCONNECT DEVICE AND FUSE REQUIREMENTS
If the optional DC subcombiner circuit breakers were not selected, then you must
provide a DC disconnect and fusing for each section (or sub-array) of the PV array.
The disconnect must be rated for the voltage and the current rating of the
photovoltaic array connected to the inverter. The DC disconnect installation must
comply with your national and local electrical code.

Wiring Requirements

You must meet the following requirements when wiring the AE 500 inverter:
Table 1‑1. Branch breaker size recommendations
Model
AE 500

WIRING INFORMATION

 Important
You must use National Electrical Code (ANSI/NFPA 70) wiring methods.
DANGER:
Do not connect the PV negative or positive conductors to the ground bus
bars provided. The PV array is grounded through the integral GFDI.
Connecting the PV array positive or negative conductors to ground at any
other point in the system would defeat the ground fault protection circuit.
1‑6
Safety and Product Compliance Guidelines
208 VAC
480 VAC
N/A
800 A
600 VAC
N/A