24 V power supply is not installed, an additional power supply will need to be
provided by the installer. The additional power supply will need to be installed
external to the inverter.
The integrated 24 V power supply meets the following specifications:
• Output voltage: 24 VDC
• Output current: 10 A
• Output wattage: 240 W
• Fuse size: 10 A
When sizing a power supply it is recommended the load not exceed 80% of name
plate capacity to prolong the life of the power supply and avoid nuisance trips caused
by inrush current. For example, if the total load capacity of all the field devices
powered by the 24 VDC power supply exceeds 80% of the rating, a second power
supply is recommended. If a second power supply is used it must be provided by the
installer and mounted external to the inverter. For this configuration, the loads must
be separated and the 24 VDC supplies isolated from each other.
Figure 4‑23. 24 V power supply terminal location

WIRING THE 24 V POWER SUPPLY

The data monitoring compartment on the upper left side of the inverter contains the
communications interface PCB. The 24 VDC terminals are located on the
communications interface PCB.
Parts or Tools Required
You need the following parts and/or tools to make the remote disable connection:
• Control voltage wire (size depends on calculated voltage drop)
• Wire stripper