MAJOR COMPONENTS AND FUNCTIONAL
PARTS
Ripple filter
DC landing
Figure 2‑1. Components of the AE 500 inverter
The modular design of the inverter makes them easy to access and service. As shown
in the preceding illustration the inverter is composed of two main sections:
• The upper compartments contains the power module assembly for the power
conversion electronics including:
◦ Power module assembly
◦ Control printed circuit boards (PCB)
◦ Power distribution PCB
◦ Power supply
◦ Active cooling system
◦ Dedicated data monitoring in the left compartment
• The lower and magnetics compartments house the following:
◦ DC combiner sub panel contains the optional DC breaker subcombiner,
optional subcombiner monitoring, and the positive, negative, and ground bars
◦ DC sub panel with the DC line filter, DC surge protection, and DC contactor
◦ AC sub panel with AC output filtering, surge protection, optional AC
disconnect, and AC connection points
◦ Magnetics compartment contains the isolation transformer and inductors
570-1001791-05A
Data monitoring
DC combiner sub panel
Product Overview
Advanced Energy® AE 500 Inverter
Air intake hood
Power module assembly
Control electronics
Display
DC sub panel
AC sub panel