Table 6‑12. Inverter model number
Inverter Model
PVP30kW
PVP35kW
PVP50kW
PVP75kW
PVP100kW
PVP250kW
PVP260kW
PVP500kW
Table 6‑13. Bit mapping for inverter configuration register
Inverter Configuration
AC volts = 208
AC volts = 240
AC volts = 480
AC volts = 600
Transformer tap position
Transformer wiring
configuration
Utility meter installation
flag
570-1001791-05A
Modbus Model Number
0272, 0273, 0274, 0288, 0289, 0290
0300, 0301, 0302, 0303
0304, 0305, 0306, 0307
0276, 0277, 0278, 0279
0280, 0281, 0282, 0283
0312, 0313, 0314, 0315, 0316, 0317, 0318, 0319
0312, 0313, 0314, 0315, 0316, 0317, 0318, 0319
0386, 0387
Bit Mapping
0x0001
0x0002
0x0004
0x0200
0x0008
0x0010
0x0100
Data Monitoring and Controls
Advanced Energy® AE 500 Inverter
Instructions
This bit is:
• Set if the tap is at 265 V
• Clear if the tap is 295 V
The default is 295 V.
This bit is:
• Set if the inverter is wired
as delta
• Clear if the inverter is
wired as wye
The default is wye.
This bit is:
• Set if the meter is installed
• Clear if the meter is not
installed
The default is not installed.