TO SHUTDOWN THE INVERTER

DANGER:
This unit contains energy storage devices that take up to 5 minutes to
discharge. Verify the high energy capacitors are completely discharged
before working on this unit.
DANGER:
Cette unité contient des dispositifs de stockage d'énergie qui prennent
jusqu'à 5 minutes pour se décharger. Vérifier que les condensateurs à haute
énergie sont complètement déchargés avant de travailler sur l'unité.
1. Turn the ON/OFF switch on the display to OFF position.
2. Turn the AC disconnect (if equipped) to the power OFF position by rotating the
AC power lever to the position shown in the following figure.
The display on the upper front panel should be inactive.
Figure 5‑10. AC disconnect power OFF
3. Open the utility connection circuit breaker.
4. Disconnect the PV array connection to the inverter using the external PV
disconnect.
5‑8
AC disconnect in power off position
Operation
570-1001791-05A