Table 9‑2. Electrical specifications
Description
AC Characteristics
Continuous AC power
Grid type
Nominal AC voltage
(VAC)
Maximum output fault
current and duration (also
known as the maximum
fault current contribution)
Maximum utility
backfeed current
AC maximum continuous
current
CEC efficiency
Peak efficiency
Frequency range
AC voltage range set
points (default)
AC operating range
Power factor at full power > 0.99
Total Harmonic
Distortion
Standby losses
DC Characteristics
DC input bus bar rating
Maximum operating input
current
note 1
MPPT range
Maximum voltage at open
circuit
Startup voltage
Startup power
note 1
At unity power factor and nominal AC voltage.
A‑2
PVP500kW: 500 kW
Three phase, four wire wye (not compatible with delta service)
480 VAC models: 480 wye
PVP500kW: 891.4 A rms at 480 VAC, 3.32 ms
PVP500kW: 3782.0 A rms at 480 VAC, 32 ms
PVP500kW: 480 VAC: 608A
PVP500kW: 480 VAC: 97.0%
PVP500kW: 480 VAC: 97.8%
59.3 Hz to 60.5 Hz
(–12% to +10%)
480 VAC models: 423 VAC to 528 VAC
< 3%
PVP500kW: < 80 W
3500 A
PVP500kW: 1600 A
310 V to 595 V
600 V
OC
330 V
PVP500kW: 1100 W
Specifications