Use grade 8, 3/8" hardware to secure the lugs of the outgoing AC cables to the
bus bars.
6. Ensure all connections are wired correctly and properly torqued. Tighten the
AC terminal screws to 40 ft-lbs.
7. Reinstall the protective plastic cover.

DC Wiring

DANGER:
Before proceeding with the DC wiring, confirm that the PV array has been
disconnected from the inverter using the external DC disconnect.
DANGER:
Avant d'effectuer les branchements CC, assurez-vous que les piles PV sont
déconnectées de l'onduleur en utilisant le connecteur CC externe.
DANGER:
Make sure the PV array polarity and voltage between the positive and
negative cables are correct before connecting the PV array cables to the DC
terminal block.
DANGER:
Assurez-vous que la polarité et le voltage des câbles positifs et négatifs des
piles PV sont corrects avant de brancher les câbles des piles PV aux bornes
CC.
The DC negative and ground bus bars are located in the lower left compartment, the
DC landing to the left of the DC combiner sub panel. The DC positive and optional
DC circuit breaker subcombiner are located in the DC combiner sub panel. The
positive, negative, and ground bus bars are vertically mounted. The positive and
negative bus bars have 18 rows of two 3/8" diameter holes spaced 1.75" apart and
four individual holes spaced 1.5 apart" vertically. The ground bar has 24 rows of two
3/8" diameter holes spaced 1.25" apart.
570-1001791-05A
Advanced Energy® AE 500 Inverter
Installing
4‑21