29.3
Enabling the Removal of the
Dedicated Power Distribution Unit
29.3.1
Active/Cold maintenance
Caution -
Open the rack door.
Disconnect all the power cords of the SPARC M10-4S and crossbar boxes
from the PDU requiring maintenance.
Note -
29.3.2
System-stopped maintenance
Open the rack door.
Stop the entire system.
Disconnect all the power cords of the SPARC M10-4S and crossbar boxes
from the PDU requiring maintenance.
Note -
Chapter 29 Maintaining the Dedicated Power Distribution Unit Mounted on the Rack for Expanded Connection
449