Note -
20.5
Installing the XSCF Interface Unit
Note -
Support the XSCF interface unit from below with one hand and then carefully
insert it into the chassis.
Raise the right and left levers and tighten the two screws.
Connect all the cables to the XSCF interface unit.
Note -
Note -
20.6
Restoring the System
Turn on the CB switches of the dedicated power distribution unit (PDU)
mounted on the rack for expanded connection.
Start the entire system.
Close the rack door.
Fujitsu M10-4/Fujitsu M10-4S/SPARC M10-4/SPARC M10-4S Service Manual ・ February 2014