Environmental specifications

The following specifications identify maximum environmental conditions. At no time
should the server run under conditions which violate these specifications.
Variable
Temperature
Humidity
Acoustic noise
Shock
Vibration
Electrostatic
discharge (ESD)
System cooling
requirement in
BTU/Hr
144
Requirements
Nonoperating: -40° to 158°F (-40° to 70°C)
Operating: 50° to 95°F (10° to 35°C) with a maximum rate of change
not to exceed 10° per hour
Nonoperating: 90% relative (noncondensing) at 95° F (35° C)
Sound Pressure: 55 dBA (Rackmount) in an idle state at typical office
ambient temperature. (73.4 +/- ° F) Sound Power: 7.0 BA in an idle
state at typical office ambient temperature. (73.4 +/- 3.6° F)
Operating - 2.0 g, 11 mSec, 1/2 sine
Unpackaged - Trapezoidal, 25 g, velocity change 136 inches/sec
(
40 lbs to > 80 lbs).
Packaged - Non-palletized free fall in height 24 inches (
> 80 lbs)
5 Hz to 500 Hz, 2.20 g RMS random
Tested to +/-15 kV, except I/O port +/- 8kV per Intel Environmental
test specification
2322 BTU/hour (Based on 520W maximum power, 78% power
subsystem efficiency, and 98% power factory correction loss)