Appendix A: Server Specifications

Environmental specifications

The following specifications identify maximum environmental conditions. At
no time should the server run under conditions which violate these
specifications.
Variable
Temperature
Altitude
Humidity
148
Requirements
Maximum rate of change: 18°F (10°C) per hour
Nonoperating: -55° to 150°F (-48.3° to 65.5°C)
Operating: 41° to 95°F (5° to 35°C); derated 0.9°F (0.5°C) for every
1,000 feet (305 meters). Use of 2 GB DIMMs derates the server to
86°F (30°C)
10,000 feet (3,048 meters) maximum
Operating wet bulb: Not to exceed 91.4°F (33 °C) (with diskette drive
or hard drive)
Nonoperating: 95% relative (noncondensing) at 86° F (30° C)