Dvi Operation - B&R PC 3100 User Manual

Panel mount device
Hide thumbs Also See for PC 3100:
Table of Contents

Advertisement

Technical data

4.1.1.2 DVI operation

In DVI operation, all signals needed to operate the Automation Panel are transferred via a separate cable. The
brightness of the display can be set using the brightness buttons.
4.1.1.2.1 DVI operation with single-touch Automation Panel
If an Automation Panel with resistive touch screen (single-touch) is operated with DVI, a DVI, USB type A/B and
RS232 cable must be connected.
Availability of the interfaces on the Automation Panel with SDL/DVI receiver:
Panel In
USB1, USB2
USB 2.0
Maximum cable length: 5 m
Requirements
• Automation Panel with SDL/DVI receiver
• Industrial PC with DVI interface
• DVI cable, USB type A/B cable, RS232 cable
4.1.1.2.2 DVI operation with multi-touch Automation Panel
If an Automation Panel with PCT touch screen (multi-touch) is operated with DVI, a DVI and USB type A/B cable
must be connected.
Availability of the interfaces on the Automation Panel with SDL/DVI receiver:
Panel In
USB1, USB2
USB 2.0
Maximum cable length: 5 m
Requirements
• Automation Panel with SDL/DVI receiver
• Industrial PC with DVI interface
• DVI cable, USB type A/B cable
4.1.1.2.3 General limitations
• Key and LED data is not transferred.
• Service and diagnostic data is not transferred.
• Updating the firmware of Automation Panels is not possible.
26
Power supply (SELV/PELV)
Single-touch Automation Panel
with SDL/DVI receiver
USB In
COM interface for touch
screen
Power supply (SELV/PELV)
Multi-touch Automation Panel
with SDL/DVI receiver
USB In
COM interface for touch
screen
DVI cable
USB type A/B cable
RS232 cable
USB 2.0
Power supply
Grounding
DVI cable
USB type A/B cable
USB 2.0
Power supply
x
Grounding
Panel PC 3100 panel mount device User's manual V 2.10
Industrial PC
Brightness controls
Industrial PC
Brightness controls