4.2.8.4 5AC901.BUPS-00

4.2.8.4.1 General information
• Battery unit for UPS IF option 5AC901.IUPS-00
• Single-cell rechargeable battery
• 2 Hawker Cyclon 12 V, 4.5 Ah rechargeable batteries connected in series
• Rated voltage 24 V
• Capacity 4.5 Ah
The battery unit is subject to wear and should be replaced regularly (after the specified service life at the latest).
Warning!
Battery unit 5AC901.BUPS-00 is only permitted to be operated with UPS IF option 5AC901.IUPS-00!
Information:
If the max. specified temperature limits of the battery unit are overshot or undershot, the temperature
alarm of the battery unit is set. Battery backing is no longer provided if the temperature alarm for the
battery unit is active. The battery is also no longer charged since this can result in damage to the
battery. This temperature alarm is defined with a hysteresis of 5°C, i.e. the temperature alarm is only
cleared again if the minimum temperature limit is again overshot by this hysteresis or the maximum
temperature limit is again undershot by this hysteresis. The temperature or temperature alarm of the
battery unit is not only monitored and checked at runtime, but also when the system is powered on;
it can be evaluated using the B&R ADI library.
4.2.8.4.2 Order data
Order number
Short description
Uninterruptible power supply
5AC901.BUPS-00
Battery unit 4.5 Ah - For UPS 5AC901.IUPS-00
Required accessories
Uninterruptible power supply
5CAUPS.0005-01
UPS cable - 0.5 m - For 5AC901.IUPS-xx
5CAUPS.0010-01
UPS cable - 1 m - For 5AC901.IUPS-xx
5CAUPS.0013-01
UPS cable - 1.3 m - For 5AC901.IUPS-xx
5CAUPS.0030-01
UPS cable - 3 m - For 5AC901.IUPS-xx
4.2.8.4.3 Technical data
Information:
The following specified characteristic data, features and limit values are only valid for this accessory
and may differ from those of the complete system. The data specified for the complete system applies
to the complete system in which this accessory is installed, for example.
Order number
General information
B&R ID code
Battery
Type
Service life
Variant
Temperature sensor
Service interval during storage
Charge duration when battery low
Certifications
CE
UKCA
UL
HazLoc
EAC
Electrical properties
Nominal voltage
Panel PC 3100 panel mount device User's manual V 2.10
5AC901.BUPS-00
0xD82E
Hawker Cyclon 12 V, 4.5 Ah, two rechargeable batteries connected in series
Up to 15 years at 20°C / 10 years at 25°C
Single cell (VRLA)
NTC resistance
Charge 1 time every 6 months
Typ. 7 hours
cULus E115267
Industrial control equipment
cULus HazLoc E180196
Industrial control equipment
for hazardous locations
Class I, Division 2, Groups ABCD, T4
Product family certification
Figure
1)
Yes
Yes
2)
24 V
Technical data