Vdc Power Supply; Grounding - B&R PC 3100 User Manual

Panel mount device
Hide thumbs Also See for PC 3100:
Table of Contents

Advertisement

4.1.6.2 +24 VDC power supply

Danger!
This device is only permitted to by supplied by a SELV/PELV power supply unit or with safety extra-low
voltage (SELV) per IEC 61010-2-201.
The necessary 3-pin connector is not included in delivery; for suitable accessories, see
The device is protected against overload and reverse polarity by a soldered fuse (15 A, fast-acting). If the fuse
is defective (e.g. due to overload), the device must be sent to B&R for repairs. If the polarity is reversed, it is not
necessary to replace the fuse.
Pin
1
2
3
Reverse polarity protection
3-pin
Male
Electrical properties
Nominal voltage
Nominal current
Overvoltage category per EN 61131-2
Inrush current
Galvanic isolation
Uninterruptible power supply
1)
IEC 61010-2-201 requirements must be observed.

4.1.6.3 Grounding

Caution!
The functional ground (power supply pin 2 and
ground connection) must be connected to the
central grounding point (e.g. control cabinet
or system) via the shortest possible path with
the lowest possible resistance and with the
largest possible wire cross section. This type of
grounding is mandatory for proper functionali-
ty.
For example, a copper strip must be attached to the ground connection at a central grounding point of the control
cabinet or system in which the device is installed. The wire cross section should be as large as possible (at least
2.5 mm²).
Panel PC 3100 panel mount device User's manual V 2.10
Description
+
Functional ground
-
Technical data
"0TB103.9x" on page
Figure
24 VDC ±25%, SELV
1)
Max. 5.5 A
II
Max. 60 A for < 300 µs
Yes
No
314.
51

Advertisement

Table of Contents
loading

Table of Contents