Information:
The automatic update only takes place if the installed firmware version differs from the upgrade ver-
sion.
Automatic downgrades are possible!
7.2.2.4 Firmware upgrade with Automation Runtime
The MTCX firmware is part of Automation Studio. The system is automatically updated to this status by Automation
Runtime.
To update the firmware contained in Automation Studio, a hardware upgrade must be performed (see
Project management / Workspace / Upgrades in Automation Help).
7.2.3 Automation Panel firmware upgrade
With Firmware upgrade (Automation Panel, SDL3 Converter, SLD4 converter), it is possible to update the firmware
of several controllers (SDLR, SDL3R, SDL4R, SDL3 Converter, SDL4 Converter) depending on the variant of the
system.
A current firmware upgrade can be downloaded directly from the Downloads section of the B&R website
(www.br-automation.com).
Caution!
The Automation Panel is not permitted to be switched off or reset while performing an upgrade!
7.2.3.1 Procedure in Windows (ADI Control Center)
1. Download the ZIP file from the B&R website (www.br-automation.com).
2. Open the ADI Control Center in the Control Panel.
3. Open tab Versions.
4. Click on the desired update under PC firmware or Panel firmware. The dialog box opens.
5. Enter the name of the firmware file or select a file under "Filename".
6. Execute file with Open.
Panel PC 3100 panel mount device User's manual V 2.10
Software
267