Digital Inputs; Digital Outputs; Analogue Inputs - Deif SGC 420 Mk II User Manual

Single genset controller
Table of Contents

Advertisement

5.6.2

Digital inputs

Digital Input #
Parameter
Source
Name
Polarity
Action
Activation
Activation Delay
5.6.3

Digital outputs

Digital outputs #
Parameter
Source
Polarity

5.6.4 Analogue inputs

Analogue Input #
Parameter
Use Input As
Calibration Table
User manual 4189341360A EN
Range
See Digital input
source selection in
this document
Auxiliary Input #
Close to Activate
Open to Activate
None
Notification
Warning
Electrical Trip
Shutdown
Never
From Engine Start
From Monitoring On
Always
0 to 60 s
Range
See Digital output
source selection in
this document
Energise
De-energise
Range
Digital input #
Lube oil pressure
Fuel level sensor
Engine coolant
temperature
Shelter temperature
sensor
Custom sensor
Resistance: 0 to 1000
Ω
Pressure: 0.0 to 10.0
Bar
Temperature: -25 to
300 °C
Fuel level: 0 to 100 %
Default
-
-
Close to Activate
None
From Monitoring On
1 s
Default
-
De-energise
Default
Not used
-
Description
Select an input source from the list.
You can configure the name of the input.
You can select how to activate the input. It can
be open or close with reference to ground.
You can configure what action occurs when the
digital input is activated.
You can configure when the controller starts to
monitor the digital input.
When the timer expires, the configured action
occurs.
Description
Select an output source from the list.
Select what the status of the output source is
when it is active. You can select if it is
energised or de-energised.
Description
Select the input.
Configure the x and y values for the 10
measurement points in the calibration table.
Page 35 of 99