Coolant Temperature Control
Parameter
Enable
Temperature Control
ON Threshold
OFF Threshold
Automatic Fuel Transfer (AFT)
Parameter
AFT Activation
Threshold
AFT deactivation
threshold
Timeout After
Activation
Monitor AFT From
Engine On
Engine Coolant Temperature
Parameter
Shutdown
Shutdown Threshold
Warning
Warning Threshold
Temp. Threshold Type
User manual 4189341360A EN
Range
Enable
Disable
Heater Control
Cooler Control
0 to 250 °C
0 to 250 °C
Range
0 to 99 %
1 to 100 %
1 to 1200 s
Enable
Disable
Range
Enable
Disable
27 to 300 °C
Enable
Disable
25 to 298 °C
Greater Than
Threshold
Less Than Threshold
Default
Not enabled
Heater Control
50 °C
50 °C
Default
40 %
80 %
600 s
Not enabled
Default
Not enabled
27 °C
Not enabled
25 °C
Greater Than
Threshold
Description
Enable this parameter to configure coolant
control.
Select the type of coolant control.
Cooler control: If the cooler temperature is
more than the ON threshold, the output for
Coolant Temperature Control is activated.
Heater control: If the heater temperature is less
than the ON threshold, the output for Coolant
Temperature Control is activated.
Cooler control: If the cooler temperature is less
than the OFF threshold, the output for Coolant
Temperature Control is deactivated.
Heater control: If the heater temperature is
more than the OFF threshold, the output for
Coolant Temperature Control is deactivated.
Description
If the fuel level is less than this threshold, the
auto fuel transfer output is activated.
If the fuel level is more than this threshold, the
output for auto fuel transfer is deactivated.
If the fuel level is less than the deactivation
threshold when this timer expires, the controller
activates a timeout alarm and deactivates the
fuel transfer output.
If this parameter is enabled, the controller
monitors the fuel level when the engine is
running.
Description
If this parameter is enabled, the controller shuts
down the engine when the temperature is more
than the shutdown set point (Shutdown
Threshold).
If the engine temperature is more than this set
point, the controller shuts down the engine.
If this parameter is enabled, the controller
activates a warning alarm when the
temperature is more than the warning set point
(Warning Threshold).
If the engine temperature is more than this set
point, the controller activates a warning alarm.
Configure if the controller activates a shutdown
and/or a warning when the monitored value is
less than or more than the set points.