Deif SGC 420 Mk II User Manual page 37

Single genset controller
Table of Contents

Advertisement

Engine Coolant Temperature
Parameter
Shutdown
Shutdown Threshold
Warning
Warning Threshold
Temp. Threshold Type
Engine Coolant Temp.
Sensor Reference
Circuit Fault Action
Shelter Temperature Monitoring
Parameter
High Temp Threshold
Shelter Temp
Hysteresis
Shelt temp Monitoring
Delay
Shelt Temp Run
Duration
Shelter Temp Sensor
Reference
Shelter Temp Fault
Action
User manual 4189341360A EN
Range
Enable
Disable
Enable
Disable
25 to 298 °C
Greater Than
Threshold
Less Than Threshold
Engine Body
Battery Negative
None
Notification
Warning
Electric trip
Shutdown
Range
25 to 300 °C
1 to 100 °C
5 to 600 s
1 to 720 min
Engine Body
Battery Negative
None
Notification
Warning
Electric trip
Shutdown
Default
Not enabled
27 °C
Not enabled
25 °C
Greater Than
Threshold
Engine Body
None
Default
60 °C
5 °C
300 s
60 min
Engine Body
None
Description
If this parameter is enabled, the controller shuts
down the engine when the engine coolant
temperature is more than/less than the
shutdown set point.
If the coolant temperature is more than/less
than this set point, the controller shuts down
the engine.
If this parameter is enabled, the controller
activates a warning alarm when the coolant
temperature is more than/less than the warning
set point.
If the coolant temperature is more than/less
than this set point, the controller activates a
warning alarm.
Configure if the controller activates a shutdown
and/or a warning when the coolant temperature
is less than or more than the set points.
The reference point for the coolant temperature
sensor.
The action for a circuit failure.
Description
The set point for a high shelter temperature. If
the shelter temperature is more than this set
point, the genset is started, and takes the load.
The shelter temperature hysteresis value. If the
shelter temperature hysteresis is less than this
set point when the genset operates,the
controller stops the genset. This is only if the
battery voltage is OK and there is a mains
failure.
If the shelter temperature is more than the set
point when the timer expires, the controller
starts the genset start sequence.
In AUTO mode, the genset operates for this
time duration when the shelter temperature is
more than the high temperature set point.
The reference point for the coolant temperature
sensor.
The action for a shelter temperature failure.
Page 37 of 99