Deif SGC 420 Mk II User Manual page 38

Single genset controller
Table of Contents

Advertisement

Analogue inputs # (sensors)
Parameter
A# Sensor Name
Shutdown
Shutdown Threshold
Warning
Warning Threshold
Threshold Type
A# Sensor Reference
Circuit Fault Action
Crank Disconnect
Parameter
Start Attempts
Disconnect on Oil
Pressure Sensor
Monitor Pressure
Sensor Before Crank
Pressure Sensor
Monitoring Threshold
Monitor Pressure
Switch Before Crank
Disconnect on Oil
Pressure Switch
Pressure Switch
Transient Time
Crank Disconnect At
Alt Frequency
User manual 4189341360A EN
Range
-
Enable
Disable
20 to 10000
Enable
Disable
30 to 10000
Greater Than
Threshold
Less Than Threshold
Engine Body
Battery Negative
None
Notification
Warning
Electric trip
Shutdown
Range
1 to 9
Enable
Disable
Enable
Disable
0.5 to 10 bar
Enable
Disable
Enable
Disable
0.0 to 3.0 s
10 to 70 Hz
Default
-
Not enabled
20
Not enabled
30
Greater Than
Threshold
Engine Body
None
Default
3
Not enabled
Not enabled
4 bar
Not enabled
Not enabled
1.5 s
20 Hz
Description
Name of the sensor. This is configurable.
If this parameter is enabled, the controller shuts
down the engine when the monitored value is
less than or more than the shutdown set point.
If the monitored value is more than or less than
this set point, the controller shuts down the
engine.
If this parameter is enabled, the controller
activates a warning alarm when the monitored
value is less than or more than the shutdown
set point.
If the monitored value is more than or less than
this set point, the controller activates a warning
alarm.
Configure if the controller activates a shutdown
and/or a warning when the coolant temperature
is less than or more than the set points.
The reference point for the coolant temperature
sensor.
The action for a circuit failure.
Description
Number of attempts to crank the engine.
If this parameter is enabled, the crank is
disconnected when the oil pressure is more
than the oil pressure set point (DISCONN LOP
SENS).
If this parameter is enabled, the oil pressure is
monitored before the engine starts. If the oil
pressure is more than the set point (MON LOP
BEF CRANK), the engine cannot start.
Configure the set point for the oil pressure.
If this parameter is enabled, the oil pressure is
monitored before the engine starts. If the
pressure switch is open, the controller activates
a high oil pressure alarm.
If this parameter is enabled, the crank
disconnects if the oil pressure is high.
If the oil pressure is high after this timer
expires, the crank is disconnected.
If the frequency is more than this set point
during cranking, the controller disconnects the
crank.
Page 38 of 99