6.2.6

Remote start/stop

You can configure digital inputs as remote start/stop inputs (latched type input). You can start and stop the genset remotely
by activating the configured remote start/stop inputs.
To configure the remote start/stop inputs, go to Digital Inputs in the smart connect software and select the source as
Remote Start/Stop. You cannot use remote start/stop when mains monitoring is enabled. Go to Mains > Configuration
and make sure the box next to Mains Monitoring is not selected.
When you activate the remote start input, the controller sends a start command to the genset. Once the genset loading
voltage and frequency are more than their minimum set points, the Warm-up delay timer starts. At the end of the warm-up
delay, the timer for the load transfer delay starts, and the genset breaker closes.
When you activate the remote stop input, the controller opens the genset breaker, and the genset cools and stops.
Minimum voltage and frequency set points
Generator > Alternator Configuration
Parameter
Min Healthy Voltage
Min Healthy Frequency
Timers
Timers > Start/Stop
Parameter
Warm-Up Delay
Load Transfer Delay
User manual 4189341360A EN
Range
10 to 100 %
10 to 100 %
Range
0 to 60 s
1 to 60 s
Default
40 %
40 %
Default
3 s
1 s
Page 61 of 99