Deif SGC 420 Mk II User Manual page 34

Single genset controller
Table of Contents

Advertisement

Auto Exercise – Event 1
Parameter
Auto Exercise
Event Occurrence
Event Day
Start Time
Duration
Load Transfer
Auto Exercise – Event 2
Parameter
Auto Exercise
Event Occurrence
Event Day
Start Time
Duration
Load Transfer
Night Mode
Parameter
Night Mode
Night Mode Start Time 00:00 to 23:59 hour
Night Mode Off
Duration
User manual 4189341360A EN
Range
Enable
Disable
Daily
Weekly
Monthly
Daily: Runs every day
Weekly: Sunday to
Saturday
Monthly: 1 to 28
00:00 to 23:59 hour
00 hr 01 min. to 99 hr
59 min.
Enable
Disable
Range
Enable
Disable
Daily
Weekly
Monthly
Daily: Runs every day
Weekly: Sunday to
Saturday
Monthly: 1 to 28
00:00 to 23:59 hours
00 hr 01 min. to 99 hr
59 min.
Enable
Disable
Range
Enable
Disable
1 to 1440 minutes
Default
Not enabled
Daily
Runs every day
10:00 hour
10 hours, 10 minutes
Not enabled
Default
Not enabled
Daily
Runs every day
09:59 hours
10 hours, 10 minutes
Not enabled
Default
Not enabled
09:00 hour
10 minutes
Description
If you enable this parameter, the controller
operates in exercise mode for the adjustable
time duration.
Configure how often the sequences occur.
Configure the start date for the sequences.
Configure the start time for the sequences.
Configure for how long the genset operates
during the scheduled sequences.
If this parameter is enabled, the load is on the
genset. If this parameter is not enabled, the
load is transferred from the genset to the
mains. This is not possible during a mains
failure.
Description
If you enable this parameter, the controller
operates in exercise mode for the adjustable
time duration.
Configure how often the sequences occur.
Configure the start date for the sequences.
Configure the start time for the sequences.
Configure for how long the genset operates
during the scheduled sequences.
If this parameter is enabled, the load is on the
genset. If this parameter is not enabled, the
load is transferred from the genset to the
mains. This is not possible during a mains
failure.
Description
In this mode, the controller is off until the night
mode timer expires. You can configure when
night mode is active.
The night mode is activated, when the start
timer starts.
Night mode is active until the Night Mode Off
timer expires.
Page 34 of 99