Cyclic Mode - Deif SGC 420 Mk II User Manual

Single genset controller
Table of Contents

Advertisement

Parameter
Shelt Temp Run Duration 0 to 720 min
Shelter Temp Sensor
Reference
Shelter Temp Fault
Action
Timers
Timers > Start/Stop
Parameter
Warm-Up Delay
Return To Mains Delay
Load Transfer Delay
Minimum voltage and frequency set points
Generator > Alternator Configuration
Parameter
Min Healthy Voltage
Min Healthy Frequency

6.2.5 Cyclic mode

In this mode, the genset operates for an adjustable amount of time during a mains failure. You can adjust the genset
operating hours and cooling down period. The maximum cycle is 12 hours.
User manual 4189341360A EN
Range
Engine Body
Battery Negative
None
Notification
Warning
Electric Trip
Shutdown
Range
0 to 60 s
0 to 600 s
1 to 60 s
Range
10 to 100 %
10 to 100 %
Default
60 min
Engine Body
None
Description
timer expires, the controller activates the
start sequence for the genset.
The genset operates for this time
duration when the shelter temperature is
too high.
Configure the reference for the shelter
temperature sensor.
Configure the action for a temperature
sensor failure.
Default
3 s
5 s
1 s
Default
40 %
40 %
Page 58 of 99