Battery Monitoring
Parameter
Low Battery Voltage
Action
Low Battery Voltage
Threshold
Low Battery Voltage
Delay
High Battery Voltage
Action
High Battery Voltage
Threshold
High Battery Voltage
Delay
Charging Alternator
Parameter
Charging Alternator
Fail Action
Charging Alternator
Fail Threshold
Charging Alternator
Fail Delay
Preheat
Parameter
Pre-heat Timer
Engine Coolant
Temperature
Engine Coolant Temp
Threshold
User manual 4189341360A EN
Range
None
Notification
Warning
Electrical Trip
Shutdown
8.0 to 31.0 V
5 to 1800 s
None
Notification
Warning
Electrical Trip
Shutdown
9.0 to 32.0 V
5 to 1800 s
Range
None
Notification
Warning
Electrical Trip
Shutdown
0.0 to 35.0 V
5 to 60 s
Range
1 to 900 s
Enable
Disable
10 to 300 °C
Default
None
8.0 V
30 s
None
15 V
30 s
Default
None
10.0 V
10 s
Default
10 s
Not enabled
25 °C
Description
Configure the action for when the battery
voltage is low.
The action for low battery voltage is activated
when the voltage load is less than this set
point.
If the battery voltage is less than the low
voltage set point (LOW VOLT THRESHOLD)
when the timer expires, the controller activates
the action for low battery voltage.
Configure the action for when the battery
voltage is high.
The action for high battery voltage is activated
when the voltage load is more than this set
point.
If the battery voltage is more than the set point
for high voltage (HIGH VOLT THRESHOLD)
when the timer expires, the controller activates
the action for high battery voltage.
Description
Configure the action for charging alternator
failure.
The action for charging alternator failure is
activated when the alternator voltage is more
than this set point.
If the alternator voltage is more than the set
point for high voltage (FAIL THRESHOLD) when
the timer expires, the controller activates the
action for charging alternator failure.
Description
When the pre-heat timer expires, the engine
starts to crank.
If this parameter is enabled, the pre-heat
output is deactivated when the engine coolant
temperature is more than the set point for the
coolant temperature (ENG TEMP LIMIT).
The set point for the engine coolant
temperature.
Page 40 of 99