5.6.5

Engine

Lube Oil Pressure (LOP)
Parameter
Shutdown
Shutdown Threshold
Warning
Threshold
LOP Sensor Reference
Circuit Fault Action
Fuel Level Monitoring
Parameter
Low Fuel Level
Shutdown
Shutdown Threshold
Low Fuel Level
Warning
Warning Threshold
Fuel Tank Capacity
Fuel Theft Warning
Fuel Theft Alarm
Threshold
Circuit Fault Action
Fuel Sensor Reference
User manual 4189341360A EN
Range
Enable
Disable
0.0 to 9.8 Bar
Enable
Disable
0.2 to 10.0 Bar
Engine Body
Battery Negative
None
Warning
Notification
Electric Trip
Shutdown
Range
Enable
Disable
0 to 78 %
Enable
Disable
2 to 80 %
2 to 6000 l
Enable
Disable
1 to 100 %/hour
None
Notification
Warning
Electric trip
Shutdown
Engine Body
Battery Negative
Default
Not enabled
2 Bar
Not enabled
3 Bar
Engine Body
None
Default
Enabled
10 %
Not enabled
12 %
100 l
Enabled
50 %/hour
None
Engine Body
Description
If this parameter is enabled, the controller shuts
down the engine when the lube oil pressure is
less than the shutdown set point (Shutdown
Threshold).
If the lube oil pressure is less than this set
point, the controller shuts down the engine.
If this parameter is enabled, the controller
activates a warning alarm when the lube oil
pressure is less than the warning set point
(Warning Threshold).
If the lube oil pressure is more than this set
point, the controller activates a warning alarm.
Configure the reference point for the sensor.
Configure the action for a circuit failure.
Description
If this parameter is enabled, the controller shuts
down the engine when the fuel level is less than
the shutdown set point.
If the oil level is less than this set point, the
controller shuts down the engine.
If this parameter is enabled, the controller
activates a warning alarm when the oil level is
less than the warning set point.
If the oil level is less than this set point, the
controller activates a warning alarm.
Configure the capacity of the fuel tank.
If the rate of fuel removal is more than the set
point for the fuel theft alarm, the controller
activates a warning alarm.
The set point for the rate of fuel removal. If the
rate is more than this set point, the controller
activates the warning alarm.
The action for a circuit failure.
The reference point for the fuel sensor.
Page 36 of 99