3. Wiring
3.1
Typical wiring
NOTE
The S2 terminals are internally short.
NOTE
The wiring diagram is an example. Use the wiring diagram for the application during installation.
Fuses
• F1: 2 A DC max. time-delay fuse/MCB, c-curve
• F4, F5: 2 A AC max. time-delay fuse/MCB, c-curve.
Relays
• Protect the breaker relays for the genset and mains against 4 kV surges as described in the IEC 61000-4-5 standard.
• Protect relay cards used with the controller against reverse battery voltages.
Communication
Communication ports for CAN (terminals 58 and 59) and RS-485 (terminals 31 and 32) have built-in 120 Ω termination
resistors.
Digital outputs
If a digital output is connected to a relay, the relay must include freewheeling diodes.