Timers - Deif SGC 420 Mk II User Manual

Single genset controller
Table of Contents

Advertisement

5.6.6

Timers

Cranking
Parameter
Crank Hold Time
Crank Rest Time
Manual Start Delay
Auto Start Delay
Run coil time
Start/Stop
Parameter
Safety Monitoring
Delay
Warm-Up Delay
Return To Mains Delay
Engine Cooling Time
Stop Action Time
Additional Stopping
Time
Load Transfer Delay
General
Parameter
Power Save Mode
Delay
Screen Changeover
Time
Deep Sleep Mode
Delay
Sounder Alarm Time
Test Mode Timer
Auto Exit Config Mode
Inlet shutoff Valve Pull
Signal
User manual 4189341360A EN
Range
1 to 255 s
2 to 60 s
0 to 300 s
0 to 43200 s
0 to 9000 s
Range
10 to 60 s
0 to 60 s
0 to 600 s
0 to 300 s
10 to 120 s
0 to 120 s
1 to 60 s
Range
5 to 1800 s
1 to 1800 s
5 to 1800 s
1 to 300 s
1 to 720 minutes
10 to 1800 s
0 to 2 s
Default
5 s
5 s
3 s
3 s
1 s
Default
10 s
3 s
5 s
5 s
30 s
10 s
1 s
Default
30 s
3 s
10 s
5 s
3 minutes
10 s
0.1 s
Description
Configure for how long the engine cranks.
The time between each crank.
When this timer expires in manual mode, the
engine starts to crank.
When this timer expires in AUTO mode, the
engine starts to crank.
The run coil timer.
Description
The engine safety parameters are not
monitored during the Safety monitoring delay.
The timer starts after crank disconnect.
When the alternator voltage and frequency are
OK, the load is transferred to the alternator.
There's a warm-up delay before the load is
transferred.
The controller closes the mains breaker when
the return to mains delay timer expires.
When the engine cooling timer expires, the
engine stops.
The time duration for the stop action sequence.
Additional time added to the engine stop
sequence.
The time it takes to transfer the load to the
mains or genset.
Description
If the controller is not in use, the backlight turns
off when the timer expires.
The display page changes when the timer
expires.
If the controller is not in use, the controller goes
into deep sleep mode when the timer expires.
The alarm is activated when the alarm output is
activated. The alarm stops when the timer
expires.
Engine run time during the test period.
If the controller is not in use, the controller
automatically exits the configuration mode
when the timer expires.
The output for the pull signal for the inlet
shutoff valve is active for this time duration.
Page 42 of 99