Deif SGC 420 Mk II User Manual page 59

Single genset controller
Table of Contents

Advertisement

To activate cyclic mode, go to Module > Cyclic Mode and tick the box next to Cyclic Mode.
During normal operations, the mains supplies the load. If there is a mains failure, the controller automatically starts the
genset and switches to generator supply (see the flowchart above). Once the genset loading voltage and frequency are
more than their minimum set points, the Warm-up delay timer starts. When the Warm-up delay timer expires, the timer for
the load transfer delay starts, and the genset breaker closes. When the mains returns, the controller synchronises the
mains breaker to the busbar when the Return to mains delay timer has expired. The genset cools and then stops.
If there is still a mains failure after the genset has cooled down and stopped, the controller starts the genset again. At the
end of the cycle, the genset cools down and then stops. This cycle continues until the mains returns. If the mains returns
during a cycle, the controller synchronises the mains breaker to the busbar when the Return to mains delay timer has
expired. The genset cools and then stops. The timer for the genset operating cycle is also reset.
You must clear all alarms before the controller can start the genset. Once you have cleared the alarms, the genset starts if
there is still a mains failure.
Module > Cyclic Mode
Parameter
Cyclic Mode
Genset Off Time
Genset On Time
User manual 4189341360A EN
Range
Enable
Disable
1 to 720 min.
1 to 720 min.
Default
Not enabled
15 min.
15 min.
Description
Tick the box to enable this mode.
Time duration for which the genset is not
in operation.
Time duration for which the genset is in
operation.
Page 59 of 99