Engine > Preheat
Parameter
Pre-heat Timer
Engine Coolant
Temperature
Engine Coolant Temp
Threshold
8.7

Other functions

8.7.1

Maintenance timer

The controller has one timer to monitor maintenance intervals.
The timer function is based on engine running hours or a due date. When the adjusted timer expires, the controller displays
an alarm.
To configure the maintenance timer, push and hold the Stop button to go to the Configuration menu. Select Maintenance.
Configuration menu > Maintenance
Parameter text
Alarm Action
Due At Engine Hours
Ash Load Enable
Alarm Due Date
8.7.2

Keyswitch

Output function
You can configure the keyswitch function with the smart connect software. Go to Digital Outputs and configure one of the
outputs as Keyswitch.
Wiring
Wire the keyswitch relay output to the ECU power. When the relay is open, the ECU has no power.
How it works
For the first 5 seconds after the SGC controller is powered on, the keyswitch relay is open.
How the keyswitch functions works:
1. There is an engine stop command.
2. The Cooling down timer starts.
3. When the cooling down timer expires, the SGC starts the Extended stop timer, and opens the keyswitch relay.
4. The relay is open until the extended stop timer expires.
User manual 4189341360A EN
Range
1 to 900 s
Enable
Disable
10 to 300 °C
Range
None
Notification
Warning
0 to 65000 hours
Enable
Disable
-
Default
10 s
Not enabled
25 °C
Description
The pre-heat function deactivates when this
timer expires.
If this parameter is enabled, the controller
deactivates the pre-heater function when
engine temperature is more than the set point
for the engine temperature (Engine Coolant
Temp Threshold).
The coolant temperature the engine must reach
during pre-heat.
Default
None
250 hours
Not enabled
Today's date
Page 84 of 99