3. Go to the Digital Outputs tab and select the output you want to use.
4. Use the drop-down list next to the output to select Coolant Temperature Control as the source.
5. Go to the Engine tab and select Coolant Temperature Control.
6. Select the tick box next to Enable to enable the coolant temperature control.
7. For Temperature Control, use the drop-down list to select Heater Control or Cooler control.
8. Configure the ON and OFF threshold.
Heater control
When the coolant temperature is less than the ON Threshold value, the output is on. When the coolant temperature is more
than the OFF Threshold value, the output is off.