6.5

Service mode

You can activate service mode via the SCB. Active charging processes are not terminated.
When the charging process is no longer active, the circuit breaker disconnects the power lines
from the supplying network for charging. Power supply to the controller and the touch screen
is maintained in this state. Now the service personnel on site can open the door of the
charging station.
In service mode, you can change different configurations of the controller. For example, it is
possible to change the limiting of power drawn from the grid and the power of the DC
charging points.
After the work is finished, close the doors. Apply or discard the changes and exit the SCB.
After you have left the SCB, the circuit breaker switches on again and the charging station
restores the readiness for charging.
For example, if you need to replace components, then you need to unlock the charging
station. The procedure for this is described in the section "Switching off the charging station
(Page 108)".
If you are working on the charging station, then observe The five safety rules for electrical
work (Page 20).
SICHARGE D
Operating Instructions, 11/2023, A5E50556539-AG
Commissioning
6.5 Service mode
109