Installation and mounting
5.6 Connecting the charging station
External emergency stop
If the charging station is integrated in the safety loop of the customer system, remove the
wire jumper between -XD36:5 and -XD36:6 and connect the signal lines here.
If an ELMS is connected, remove the wire jumper between XD36:7 and XD36:8 and connect
the signal lines here.
Figure 5-33  Connections for external emergency stop
External load management system
In addition to the signal cables for the emergency stop, the communication cable must be
connected to ‑FA13.
The WAN port of Router 1 (-XF3) must be reconfigured to VLAN in the SCB so that
communication up to the controller can be established. See section "Routers (Page 53)":
• VLAN IP: 10.20.37.1...255
• Port: 400
Ensure that the ELMS is set to the same address range.
102
Operating Instructions, 11/2023, A5E50556539-AG