Electrical installation
Installer reference guide
98
1N~
3 Fix the cables with cable ties to the cable tie mountings.
In case of preferential kWh rate power supply
Preferential kWh rate
power supply
Separate normal kWh
rate power supply
Preferential kWh rate
power supply contact
[9.8] Benefit kWh power supply
1 Open the service cover. See
2 Connect the preferential kWh rate power supply (1N~or 3N~ depending on
model, see name plate).
3N~
OR
L N
L1 L2 L3 N
X1M
Wires: 1N+GND, OR 3N+GND
Maximum running current: Refer to name plate on
unit.
Wires: 1N
Maximum running current: 6.3 A
Wires: 2×(0.75~1.25 mm²)
Maximum length: 50 m.
Preferential kWh rate power supply contact:
16 V DC detection (voltage supplied by PCB). The
voltage-free contact shall ensure the minimum
applicable load of 15 V DC, 10 mA.
"7.3.2 To open the outdoor
1N~
OR
Q1DI
Q1DI
L N PE
N
L1
1N~, 50 Hz,
220-240 V AC
4
unit" [
 72].
3N~
L2
L3
N PE
3N~, 50 Hz,
380-415 V AC
EBLA09~16D + EDLA09~16D
Daikin Altherma 3 M
4P620241-1B – 2022.05