Daikin EBLA09D V3 Series Installer's Reference Manual page 17

Hide thumbs Also See for EBLA09D V3 Series:
Table of Contents

Advertisement

EBLA09~16D + EDLA09~16D
Daikin Altherma 3 M
4P620241-1B – 2022.05
WARNING
All wiring MUST be performed by an authorised electrician and MUST comply
with the applicable legislation.
Make electrical connections to the fixed wiring.
All components procured on-site and all electrical construction MUST comply
with the applicable legislation.
WARNING
If the power supply has a missing or wrong N-phase, equipment might break
down.
Establish proper earthing. Do NOT earth the unit to a utility pipe, surge absorber,
or telephone earth. Incomplete earthing may cause electrical shock.
Install the required fuses or circuit breakers.
Secure the electrical wiring with cable ties so that the cables do NOT come in
contact with sharp edges or piping, particularly on the high-pressure side.
Do NOT use taped wires, stranded conductor wires, extension cords, or
connections from a star system. They can cause overheating, electrical shock or
fire.
Do NOT install a phase advancing capacitor, because this unit is equipped with an
inverter. A phase advancing capacitor will reduce performance and may cause
accidents.
WARNING
Rotating fan. Before powering ON the outdoor unit, make sure that the discharge
grille covers the fan as protection against a rotating fan. See
discharge
grille" [
CAUTION
Do NOT push or place redundant cable length into the unit.
WARNING
The backup heater MUST have a dedicated power supply and MUST be protected by
the safety devices required by the applicable legislation.
CAUTION
To guarantee the unit is completely earthed, ALWAYS connect the backup heater
power supply and the earth cable.
WARNING
Stripped wire. Make sure that stripped wire cannot make contact with possible
water on the bottom plate.
"11 Configuration" [
Configuration (see
CAUTION
The disinfection function settings MUST be configured by the installer according to
the applicable legislation.
3
Specific installer safety instructions
|
4
 71].
4
 123])
"7.2.6  To install the
Installer reference guide
17

Advertisement

Table of Contents
loading

Table of Contents