Daikin Altherma 3 M User Reference Manual

Daikin Altherma 3 M User Reference Manual

Hide thumbs Also See for Altherma 3 M:
Table of Contents

Advertisement

EBLA09~16DAV3
EBLA09~16DAW1
EBLA09~16DA3V3
EBLA09~16DA3W1
User reference guide
Daikin Altherma 3 M
EDLA09~16DAV3
EDLA09~16DAW1
EDLA09~16DA3V3
EDLA09~16DA3W1

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Altherma 3 M and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Daikin Altherma 3 M

  • Page 1 User reference guide Daikin Altherma 3 M EBLA09~16DAV3 EDLA09~16DAV3 EBLA09~16DAW1 EDLA09~16DAW1 EBLA09~16DA3V3 EDLA09~16DA3V3 EBLA09~16DA3W1 EDLA09~16DA3W1...
  • Page 2: Table Of Contents

    Symptom: You are feeling too cold (hot) in your living room..................58 Symptom: The water at the tap is too cold........................58 Symptom: Heat pump failure ............................59 User reference guide EBLA09~16DA + EDLA09~16DA Daikin Altherma 3 M 4P620245-1 – 2020.06...
  • Page 3 Overview: Relocation ..............................61 10 Disposal 11 Glossary 12 Installer settings: Tables to be filled in by installer 12.1 Configuration wizard............................... 64 12.2 Settings menu ................................. 65 EBLA09~16DA + EDLA09~16DA User reference guide Daikin Altherma 3 M 4P620245-1 – 2020.06...
  • Page 4: About This Document

    Format: Paper (in the box of the outdoor unit) + Digital files on http:// www.daikineurope.com/support-and-manuals/product-information/ Latest revisions of the supplied documentation may be available on the regional Daikin website or via your installer. The original documentation is written in English. All other languages are translations. EBLA09~16DA + EDLA09~16DA...
  • Page 5: Meaning Of Warnings And Symbols

    About this document Daikin Residential Controller app If set up by your installer, you can use the Daikin Residential Controller app to control and monitor the status of your system. For more information, see: http://www.onlinecontroller.daikineurope.com/ Breadcrumbs Breadcrumbs (example: [4.3]) help you to locate where you are in the menu structure of the user interface.
  • Page 6 Example: " 1–3 Figure title" means "Figure 3 in chapter 1". Indicates a table title or a reference to it. Example: " 1–3 Table title" means "Table 3 in chapter 1". EBLA09~16DA + EDLA09~16DA User reference guide Daikin Altherma 3 M 4P620245-1 – 2020.06...
  • Page 7: User Safety Instructions

    Do NOT place any objects containing water on the unit. CAUTION ▪ Do NOT place any objects or equipment on top of the unit. ▪ Do NOT sit, climb or stand on the unit. EBLA09~16DA + EDLA09~16DA User reference guide Daikin Altherma 3 M 4P620245-1 – 2020.06...
  • Page 8: Instructions For Safe Operation

    Do NOT use cleaning materials or means to accelerate the defrosting process other than those recommended by the manufacturer. ▪ Be aware that the refrigerant inside the system is odourless. EBLA09~16DA + EDLA09~16DA User reference guide Daikin Altherma 3 M 4P620245-1 – 2020.06...
  • Page 9 Reason: Refrigerant might leak into the water circuit, and subsequently into the room when you purge air from the heat emitters or collectors. EBLA09~16DA + EDLA09~16DA User reference guide Daikin Altherma 3 M 4P620245-1 – 2020.06...
  • Page 10: About The System

    Underfloor heating c Heat pump convectors or fan coil units d User interface e Dedicated Human Comfort Interface (BRC1HHDA used as room thermostat) f Domestic hot water (DHW) tank EBLA09~16DA + EDLA09~16DA User reference guide Daikin Altherma 3 M 4P620245-1 – 2020.06...
  • Page 11: Quick Guide

    The User pin code is 0000. User 0000 Advanced user pin code The Advanced user pin code is 1234. Additional menu items for the user are now visible. Advanced user 1234 EBLA09~16DA + EDLA09~16DA User reference guide Daikin Altherma 3 M 4P620245-1 – 2020.06...
  • Page 12: Space Heating/Cooling

    During room temperature control, you can use the room temperature setpoint screen to read out and adjust the desired room temperature. 1 Go to [1]: Room. Room EBLA09~16DA + EDLA09~16DA User reference guide Daikin Altherma 3 M 4P620245-1 – 2020.06...
  • Page 13 1 Go to the applicable zone: Zone Go to … Main zone – Heating [2.5] Main zone > Heating WD curve Main zone – Cooling [2.6] Main zone > Cooling WD curve EBLA09~16DA + EDLA09~16DA User reference guide Daikin Altherma 3 M 4P620245-1 – 2020.06...
  • Page 14 Possible actions on this screen Go through the temperatures. Change the temperature. Go to the next temperature. Confirm changes and proceed. More information For more information, see also: EBLA09~16DA + EDLA09~16DA User reference guide Daikin Altherma 3 M 4P620245-1 – 2020.06...
  • Page 15 Quick guide ▪ "5.4 Turning operation ON or OFF" [  25] ▪ "5.6 Space heating/cooling control" [  28] ▪ "5.8 Preset values and schedules" [  35] ▪ "5.9 Weather-dependent curve" [  46] EBLA09~16DA + EDLA09~16DA User reference guide Daikin Altherma 3 M 4P620245-1 – 2020.06...
  • Page 16: Domestic Hot Water

    [5.3] and Reheat setpoint [5.4]. More information For more information, see also: ▪ "5.4 Turning operation ON or OFF" [  25] ▪ "5.7 Domestic hot water control" [  32] ▪ "5.8 Preset values and schedules" [  35] EBLA09~16DA + EDLA09~16DA User reference guide Daikin Altherma 3 M 4P620245-1 – 2020.06...
  • Page 17: Operation

    Slot for WLAN cartridge With the WLAN cartridge, the installer can connect the system to the internet. As user you can then control the system via the Daikin Residential Controller app. Note: This slot cannot be used for SD cards.
  • Page 18 : Turn the right dial. Navigate through the possible values and settings. ▪ : Press the right dial. Confirm your choice and go to the next menu item. EBLA09~16DA + EDLA09~16DA User reference guide Daikin Altherma 3 M 4P620245-1 – 2020.06...
  • Page 19: Menu Structure: Overview User Settings

    (**) Only accessible by installer (***) Only applicable when WLAN is installed INFORMATION Depending on the selected installer settings and unit type, settings will be visible/ invisible. EBLA09~16DA + EDLA09~16DA User reference guide Daikin Altherma 3 M 4P620245-1 – 2020.06...
  • Page 20: Possible Screens: Overview

    26 Feb 2020 22:19 Possible actions on this screen Go through the list of the main menu. Go to the main menu screen. Enable/disable breadcrumbs. EBLA09~16DA + EDLA09~16DA User reference guide Daikin Altherma 3 M 4P620245-1 – 2020.06...
  • Page 21 Smart energy is currently being used for domestic hot water. Space operation mode Cooling Heating Outdoor / quiet mode Measured outdoor temperature Quiet mode active Outdoor unit Domestic hot water tank Standalone tank installed EBLA09~16DA + EDLA09~16DA User reference guide Daikin Altherma 3 M 4P620245-1 – 2020.06...
  • Page 22 "8.1 To display the help text in case of a malfunction" [  57] for more information. If the corresponding operation (for example: space heating) is not active, the circle is greyed out. EBLA09~16DA + EDLA09~16DA User reference guide Daikin Altherma 3 M 4P620245-1 – 2020.06...
  • Page 23: Main Menu Screen

    User settings mode and quiet mode. Displays data and information about the Information outdoor unit. Installer settings Restriction: Only for the installer. Gives access to advanced settings. EBLA09~16DA + EDLA09~16DA User reference guide Daikin Altherma 3 M 4P620245-1 – 2020.06...
  • Page 24: Setpoint Screen

    Wireless gateway Restriction: Only displayed if a wireless LAN (WLAN) is installed. Contains settings needed when configuring the Daikin Residential Controller app. 5.3.3 Setpoint screen The setpoint screen is displayed for screens describing system components that need a setpoint value.
  • Page 25: Detailed Screen With Values

    Certain functionalities of the unit can be enabled or disabled separately. If a functionality is disabled, the corresponding temperature icon in the home screen will be greyed out. Room temperature control Room temperature control ON Room temperature control OFF EBLA09~16DA + EDLA09~16DA User reference guide Daikin Altherma 3 M 4P620245-1 – 2020.06...
  • Page 26: To Turn On Or Off

    NOTICE Water pipe freeze prevention. Even if you turn OFF space heating/cooling operation ([C.2]: Operation > Space heating/cooling), water pipe freeze prevention –if enabled– will remain active. EBLA09~16DA + EDLA09~16DA User reference guide Daikin Altherma 3 M 4P620245-1 – 2020.06...
  • Page 27: Reading Out Information

    Example: Defrost/oil return mode [8.7] About Version information about the system [8.8] Connection status Information about the connection status of the unit, the room thermostat and WLAN. EBLA09~16DA + EDLA09~16DA User reference guide Daikin Altherma 3 M 4P620245-1 – 2020.06...
  • Page 28: Space Heating/Cooling Control

    When the unit is not in operation, the status indicator will show a blue pulsation with an interval of approximately 5 seconds. ▪ While the unit is in operation, the status indicator will light up blue constantly. EBLA09~16DA + EDLA09~16DA User reference guide Daikin Altherma 3 M 4P620245-1 – 2020.06...
  • Page 29: Determining Which Temperature Control You Are Using

    Check the installer settings table filled in by the installer. To determine which temperature control you are using (method 2) You can see on the home screen which temperature control you are using. EBLA09~16DA + EDLA09~16DA User reference guide Daikin Altherma 3 M 4P620245-1 – 2020.06...
  • Page 30: To Change The Desired Room Temperature

    The desired room temperature will return to its scheduled value whenever a scheduled action occurs. You can avoid scheduled behaviour by (temporarily) turning off scheduling. To turn off room temperature scheduling 1 Go to [1.1]: Room > Schedule. EBLA09~16DA + EDLA09~16DA User reference guide Daikin Altherma 3 M 4P620245-1 – 2020.06...
  • Page 31: To Change The Desired Leaving Water Temperature

    You can avoid scheduled behaviour by (temporarily) turning off scheduling. To turn off leaving water temperature scheduling 1 Go to one of the following: ▪ [2.1]: Main zone > Schedule ▪ [3.1]: Additional zone > Schedule EBLA09~16DA + EDLA09~16DA User reference guide Daikin Altherma 3 M 4P620245-1 – 2020.06...
  • Page 32: Domestic Hot Water Control

    To determine which domestic hot water mode you are using (method 2) 1 Go to [5]: Tank. 2 Check which items are displayed: [5.1] Powerful operation [5.2] Comfort setpoint [5.3] Eco setpoint [5.4] Reheat setpoint [5.5] Schedule EBLA09~16DA + EDLA09~16DA User reference guide Daikin Altherma 3 M 4P620245-1 – 2020.06...
  • Page 33: Reheat Mode

    The best time to allow the tank to produce hot water is at night, because the space heating demand is lower. Example: 60°C 50°C 40°C 15°C 00:00 07:00 14:00 21:00 DHW tank temperature Time EBLA09~16DA + EDLA09~16DA User reference guide Daikin Altherma 3 M 4P620245-1 – 2020.06...
  • Page 34: Scheduled + Reheat Mode

    1 Go to [5]: Tank. Tank 2 Adjust the domestic hot water temperature. °C – Tank a Actual domestic hot water temperature b Desired domestic hot water temperature EBLA09~16DA + EDLA09~16DA User reference guide Daikin Altherma 3 M 4P620245-1 – 2020.06...
  • Page 35: Using Dhw Powerful Operation

    If you later want to change the value, you only have to do it in one place. Possible preset values You can set the following user-defined preset values: EBLA09~16DA + EDLA09~16DA User reference guide Daikin Altherma 3 M 4P620245-1 – 2020.06...
  • Page 36: Using And Programming Schedules

    "Possible actions" in "Using and predefined schedules are not satisfactory. programming schedules The actions you can program are control " [  37] specific. ▪ "5.8.3  Schedule screen: Example" [  40] EBLA09~16DA + EDLA09~16DA User reference guide Daikin Altherma 3 M 4P620245-1 – 2020.06...
  • Page 37 [1.3] Room > Cooling Predefined schedules: 1 schedule Activation screen: [1.1] Schedule Schedule for the desired room Possible actions: Temperatures within range. temperature in cooling mode. EBLA09~16DA + EDLA09~16DA User reference guide Daikin Altherma 3 M 4P620245-1 – 2020.06...
  • Page 38 "5.6.2 Setting the space operation cooling > Operation mode mode" [  28]. schedule Schedule (per month) for when to operate the unit in heating mode and when in cooling mode. EBLA09~16DA + EDLA09~16DA User reference guide Daikin Altherma 3 M 4P620245-1 – 2020.06...
  • Page 39 Possible actions: You can program 2 actions per > Booster heater > BSH day. allowance schedule ▪ Off: Booster heater operation NOT allowed. ▪ On: Booster heater operation allowed. EBLA09~16DA + EDLA09~16DA User reference guide Daikin Altherma 3 M 4P620245-1 – 2020.06...
  • Page 40: Schedule Screen: Example

    To clear the content of the week schedule 1 Select the name of the current schedule. User defined 1 2 Select Delete. Delete Rename Select 3 Select OK to confirm. EBLA09~16DA + EDLA09~16DA User reference guide Daikin Altherma 3 M 4P620245-1 – 2020.06...
  • Page 41 In this example, Monday is the first day you programmed. Thus, the last programmed action is valid up to the first action of next Monday. EBLA09~16DA + EDLA09~16DA User reference guide Daikin Altherma 3 M 4P620245-1 – 2020.06...
  • Page 42 5 Repeat this action for all other weekdays. — User defined 1 To program the schedule for Saturday and copy it to Sunday 1 Select Saturday. 2 Select Edit. EBLA09~16DA + EDLA09~16DA User reference guide Daikin Altherma 3 M 4P620245-1 – 2020.06...
  • Page 43 INFORMATION Not all schedules can be renamed. Usage example: You work in a 3-shift system If you work in a 3-shift system, you can do the following: EBLA09~16DA + EDLA09~16DA User reference guide Daikin Altherma 3 M 4P620245-1 – 2020.06...
  • Page 44: Setting The Energy Prices

    2 Program the selection using the scheduling screen. You can set — the High, Medium and Low electricity prices according to your electricity supplier. 3 Confirm the changes. EBLA09~16DA + EDLA09~16DA User reference guide Daikin Altherma 3 M 4P620245-1 – 2020.06...
  • Page 45 Gas price=4.08+(5×0.9) Gas price=8.58 Calculation of the electricity price Electricity price=Actual electricity price+Incentive/kWh Electricity price=12.49+5 Electricity price=17.49 Price Value in breadcrumb Gas: 4.08 /kWh [7.6]=8.6 Electricity: 12.49 /kWh [7.5.1]=17 EBLA09~16DA + EDLA09~16DA User reference guide Daikin Altherma 3 M 4P620245-1 – 2020.06...
  • Page 46: Weather-Dependent Curve

    See "5.9.4 Using weather-dependent curves" [  49]. 5.9.2 2-points curve Define the weather-dependent curve with these two setpoints: ▪ Setpoint (X1, Y2) ▪ Setpoint (X2, Y1) EBLA09~16DA + EDLA09~16DA User reference guide Daikin Altherma 3 M 4P620245-1 – 2020.06...
  • Page 47: Slope-Offset Curve

    Examples Weather-dependent curve when slope is selected: EBLA09~16DA + EDLA09~16DA User reference guide Daikin Altherma 3 M 4P620245-1 – 2020.06...
  • Page 48 The icon corresponds to the heat emitter for that zone: ▪ : Underfloor heating ▪ : Fan coil unit ▪ : Radiator ▪ : Domestic hot water tank EBLA09~16DA + EDLA09~16DA User reference guide Daikin Altherma 3 M 4P620245-1 – 2020.06...
  • Page 49: Using Weather-Dependent Curves

    [2.5] Main zone > Heating WD curve Main zone – Cooling [2.6] Main zone > Cooling WD curve Additional zone – Heating [3.5] Additional zone > Heating WD curve EBLA09~16DA + EDLA09~16DA User reference guide Daikin Altherma 3 M 4P620245-1 – 2020.06...
  • Page 50 Cold Cold ↑ ↑ ↑ ↑ Cold ↓ ↑ ↓ ↑ — ↓ — ↓ Cold ↑ ↓ ↑ ↓ ↓ ↓ ↓ ↓ "5.9.2 2-points curve" [  46]. EBLA09~16DA + EDLA09~16DA User reference guide Daikin Altherma 3 M 4P620245-1 – 2020.06...
  • Page 51: Other Functionalities

    While holiday mode is active, space heating/cooling operation and domestic hot water operation will be turned off. Room frost protection, water pipe freeze prevention and anti-legionella operation will remain active. EBLA09~16DA + EDLA09~16DA User reference guide Daikin Altherma 3 M 4P620245-1 – 2020.06...
  • Page 52: Using Wlan

    About the WLAN cartridge The WLAN cartridge connects the system to the internet. As user you can then control the system via the Daikin Residential Controller app. This needs the following components: EBLA09~16DA + EDLA09~16DA User reference guide Daikin Altherma 3 M 4P620245-1 –...
  • Page 53 The Daikin Residential Controller app needs to be installed on the user's smartphone. See: http://www.onlinecontroller.daikineurope.com/ Configuration To configure the Daikin Residential Controller app, follow the in-app instructions. While doing this, the following actions and information are needed on the user interface: [D] Wireless gateway...
  • Page 54 [D.6] Cloud connection: Read out the status of the connection to the cloud: 1 Go to [D.6]: Wireless gateway > Cloud connection. 2 Read out the connection status: ▪ Not connected ▪ Connected EBLA09~16DA + EDLA09~16DA User reference guide Daikin Altherma 3 M 4P620245-1 – 2020.06...
  • Page 55: Energy Saving Tips

    Program to turn ON the domestic hot water pump only during periods of the day when instant hot water is necessary. Example: In the morning and evening. EBLA09~16DA + EDLA09~16DA User reference guide Daikin Altherma 3 M 4P620245-1 – 2020.06...
  • Page 56: Maintenance And Service

    Turn off any combustible heating devices, ventilate the room, and contact the dealer where you purchased the unit. Do NOT use the unit until a service person confirms that the part from which the refrigerant leaked has been repaired. EBLA09~16DA + EDLA09~16DA User reference guide Daikin Altherma 3 M 4P620245-1 – 2020.06...
  • Page 57: Troubleshooting

    Conditions: The user permission level is set to advanced end user. 1 Go to [8.2]: Information > Malfunction history. You see a list of the most recent malfunctions. EBLA09~16DA + EDLA09~16DA User reference guide Daikin Altherma 3 M 4P620245-1 – 2020.06...
  • Page 58: Symptom: You Are Feeling Too Cold (Hot) In Your Living Room

    DHW tank to a preset value (Eco setpoint = lower tank temperature) during the day. "5.8.2  Using programming schedules"  [   36] and "5.8.3  Schedule screen: Example" [  40]. EBLA09~16DA + EDLA09~16DA User reference guide Daikin Altherma 3 M 4P620245-1 – 2020.06...
  • Page 59: Symptom: Heat Pump Failure

    We recommend to purge air with the air purge function of the unit (to be performed by the installer). If you purge air from the heat emitters or collectors, mind the following: EBLA09~16DA + EDLA09~16DA User reference guide Daikin Altherma 3 M 4P620245-1 – 2020.06...
  • Page 60 If yes, make sure that the room where you want to purge air is sufficiently ventilated. Reason: Refrigerant might leak into the water circuit, and subsequently into the room when you purge air from the heat emitters or collectors. EBLA09~16DA + EDLA09~16DA User reference guide Daikin Altherma 3 M 4P620245-1 – 2020.06...
  • Page 61: Relocation

    If you want to relocate parts of your system, contact your installer. You can find the contact/helpdesk number via the user interface. 1 Go to [8.3]: Information > Dealer information. EBLA09~16DA + EDLA09~16DA User reference guide Daikin Altherma 3 M 4P620245-1 – 2020.06...
  • Page 62: Disposal

    Do NOT try to dismantle the system yourself: dismantling of the system, treatment of the refrigerant, oil and other parts MUST comply with applicable legislation. Units MUST be treated at a specialised treatment facility for reuse, recycling and recovery. EBLA09~16DA + EDLA09~16DA User reference guide Daikin Altherma 3 M 4P620245-1 – 2020.06...
  • Page 63: Glossary

    Optional equipment Equipment made or approved by Daikin that can be combined with the product according to the instructions in the accompanying documentation. Field supply Equipment NOT made by Daikin that can be combined with the product according to the instructions in the accompanying documentation.
  • Page 64: Installer Settings: Tables To Be Filled In By Installer

    Additional zone (only if [4.4]=1, dual zone) Emitter type [3.7] Control (read only) [3.9] Setpoint mode [3.4] Schedule [3.1] WD curve type [3.C] (read only) Tank (if applicable) EBLA09~16DA + EDLA09~16DA User reference guide Daikin Altherma 3 M 4P620245-1 – 2020.06...
  • Page 65: Settings Menu

    WD curve type [5.E] (read only) 12.2 Settings menu Setting Fill in… Main zone Thermostat type [2.A] Additional zone (if applicable) Thermostat type [3.A] Information Dealer information [8.3] EBLA09~16DA + EDLA09~16DA User reference guide Daikin Altherma 3 M 4P620245-1 – 2020.06...
  • Page 68 4P620245-1 2020.06 Verantwortung für Energie und Umwelt...

This manual is also suitable for:

Ebla09-16dav3Ebla09-16daw1Ebla09-16da3v3Ebla09-16da3w1