Daikin EBLA09D V3 Series Installer's Reference Manual page 226

Hide thumbs Also See for EBLA09D V3 Series:
Table of Contents

Advertisement

12
|
Commissioning
Installer reference guide
226
NOTICE
When purging air with the manual air purge valve of the unit, collect any fluid that
might leak out of the valve. If this fluid is NOT collected, it might drip on internal
components and damage the unit.
INFORMATION
To purge air, use all air purge valves present in the system. This includes the
automatic or manual air purge valve of the outdoor unit, as well as any field-
supplied valves.
If the system contains an external backup heater kit, also use the air purge valve
of the backup heater.
If the system contains valve kit EKMBHBP1, it is required to – during the air purge
– manually switch the position of the valve kit's 3‑way valve by turning its knob,
this to prevent air from remaining in the bypass. For more information, see
"9.2.4 External backup heater
INFORMATION
Start by performing a manual air purge. When almost all the air is removed, perform
an automatic air purge. If necessary, repeat performing the automatic air purge until
you are sure that all air is removed from the system. During air purge function, pump
speed limitation [9‑0D] is NOT applicable.
The air purge function automatically stops after 30 minutes.
INFORMATION
For best results, air purge each loop separately.
To perform a manual air purge
Conditions: Make sure all operation is disabled. Go to [C]: Operation and turn off
Space heating/cooling and Tank operation.
1 Set the user permission level to Installer. See
the user permission
2 Go to [A.3]: Commissioning > Air purge.
3 In the menu, set Type = Manual.
4 Select Start air purge.
5 Select OK to confirm.
Result: The air purge starts. It stops automatically when ready.
6 During manual operation:
You can change the pump speed.
You must change the circuit.
To change these settings during the air purge, open the menu
and go to [A.3.1.5]: Settings.
Scroll to Circuit and set it to Space/Tank.
Scroll to Pump speed and set it to Low/High.
kit" [
4
 101].
4
level" [
 124].
"To change
EBLA09~16D + EDLA09~16D
Daikin Altherma 3 M
4P620241-1B – 2022.05