Field settings table
Breadcrumb Field code
Setting name
9.I
[0-0B]
Leaving water value for high ambient temp. for DHW WD curve.
9.I
[0-0C]
Leaving water value for low ambient temp. for DHW WD curve.
9.I
[0-0D]
High ambient temp. for DHW WD curve.
9.I
[0-0E]
Low ambient temp. for DHW WD curve.
9.I
[1-00]
Low ambient temp. for LWT main zone heating WD curve.
9.I
[1-01]
High ambient temp. for LWT main zone heating WD curve.
9.I
[1-02]
Leaving water value for low ambient temp. for LWT main zone heating WD curve.
9.I
[1-03]
Leaving water value for high ambient temp. for LWT main zone heating WD curve.
9.I
[1-04]
Weather dependent cooling of the main leaving water temperature zone.
9.I
[1-05]
Weather dependent cooling of the additional leaving water temperature zone
9.I
[1-06]
Low ambient temp. for LWT main zone cooling WD curve.
9.I
[1-07]
High ambient temp. for LWT main zone cooling WD curve.
9.I
[1-08]
Leaving water value for low ambient temp. for LWT main zone cooling WD curve.
9.I
[1-09]
Leaving water value for high ambient temp. for LWT main zone cooling WD curve.
9.I
[1-0A]
What is the averaging time for the outdoor temp?
9.I
[1-0B]
What is the desired delta T in heating for the main zone?
9.I
[1-0C]
What is the desired delta T in heating for the additional zone?
9.I
[1-0D]
What is the desired delta T in cooling for the main zone?
9.I
[1-0E]
What is the desired delta T in cooling for the additional zone?
9.I
[2-00]
When should the disinfection function be executed?
9.I
[2-01]
Should the disinfection function be executed?
9.I
[2-02]
When should the disinfection function start?
9.I
[2-03]
What is the disinfection target temperature?
9.I
[2-04]
How long must the tank temperature be maintained?
9.I
[2-05]
Room antifrost temperature
9.I
[2-06]
Room frost protection
9.I
[2-09]
Adjust the offset on the measured room temperature
9.I
[2-0A]
Adjust the offset on the measured room temperature
9.I
[2-0B]
What is the required offset on the measured outdoor temp.?
9.I
[2-0C]
What emitter type is connected to the main LWT zone?
9.I
[2-0D]
What emitter type is connected to the additional LWT zone?
9.I
[2-0E]
What is the maximum allowed current over the heatpump ?
9.I
[3-00]
Is auto restart of the unit allowed?
9.I
[3-01]
--
9.I
[3-02]
--
9.I
[3-03]
--
9.I
[3-04]
--
9.I
[3-05]
--
9.I
[3-06]
What is the maximum desired room temperature in heating?
9.I
[3-07]
What is the mimimum desired room temperature in heating?
9.I
[3-08]
What is the maximum desired room temperature in cooling?
9.I
[3-09]
What is the minimum desired room temperature in cooling?
9.I
[4-00]
What is the BUH operation mode?
9.I
[4-01]
Which electric heater has priority?
(*1) *V3/W1*
(*2) *3V3/3W1*
(*3) EDLA*
(*4) EBLA*
Range, step
Default value
R/W
35~[6-0E]°C, step: 1°C
55°C
R/W
45~[6-0E]°C, step: 1°C
55°C
R/W
10~25°C, step: 1°C
15°C
R/W
-40~5°C, step: 1°C
-10°C
R/W
-40~5°C, step: 1°C
-10°C
R/W
10~25°C, step: 1°C
15°C
R/W
[9-01]~[9-00], step: 1°C
35°C
R/W
[9-01]~min(45, [9-00])°C , step: 1°C
25°C
R/W
0: Disabled
1: Enabled
R/W
0: Disabled
1: Enabled
R/W
10~25°C, step: 1°C
20°C
R/W
25~43°C, step: 1°C
35°C
R/W
[9-03]~[9-02]°C, step: 1°C
22°C
R/W
[9-03]~[9-02]°C, step: 1°C
18°C
R/W
0: No averaging
1: 12 hours
2: 24 hours
3: 48 hours
4: 72 hours
R/W
[2-0C] ≠2 (Radiator)
3~10°C, step: 1°C
5°C
[2-0C] = 2 (Radiator)
8°C
R/W
[2-0D] ≠2 (Radiator)
3~10°C, step: 1°C
5°C
[2-0D] = 2 (Radiator)
8°C
R/W
3~10°C, step: 1°C
5°C
R/W
3~10°C, step: 1°C
5°C
R/W
0: Each day
1: Monday
2: Tuesday
3: Wednesday
4: Thursday
5: Friday
6: Saturday
7: Sunday
R/W
0: No
1: Yes
R/W
0~23 hour, step: 1 hour
1
R/W
55~75°C, step: 5°C
70°C
R/W
5~60 min, step: 5 min
10 min
R/W
4~16°C, step: 1°C
8°C
R/W
0: Disabled
1: Enabled
R/W
-5~5°C, step: 0,5°C
0°C
R/W
-5~5°C, step: 0,5°C
0°C
R/W
-5~5°C, step: 0,5°C
0°C
R/W
0: Underfloor heating
1: Fancoil unit
2: Radiator
R/W
0: Underfloor heating
1: Fancoil unit
2: Radiator
R/W
20~50 A, step: 1 A
50 A
R/W
0: No
1: Yes
0
1
4
2
1
R/W
18~30°C, step: 1°C
30°C
R/W
12~18°C, step: 1°C
12°C
R/W
25~35°C, step: 1°C
35°C
R/W
15~25°C, step: 1°C
15°C
R/W
0: Disabled
1: Enabled
2: Only DHW
R/W
0: None
1: BSH
2: BUH
7/11
Installer setting at variance with
default value
Date
Value
4P627273-1B - 2022.05