11
|
Configuration
Power consumption control
Installer reference guide
206
Smart Grid contact
1
1
1
Free running:
The Smart Grid function is NOT active.
Forced off:
The unit forces OFF the compressor and the heaters (backup heater, booster
heater).
The protective functions (water pipe freeze prevention, drain prevention, room
frost protection, tank disinfection) and defrost are NOT overruled (capacity will
not be limited for these functions)
Recommended on:
In case the space heating/cooling request is OFF and the tank temperature
setpoint is reached, the unit can choose to buffer energy from the photovoltaic
panels in the room (only in case of room thermostat control) or in the DHW tank
instead of putting the photovoltaic panel energy on the grid.
In case of room buffering, the room will heat up or cool down to the comfort
setpoint. In case of tank buffering, the tank will heat up to the maximum tank
temperature.
The goal is to buffer the energy from the photovoltaic panels. Therefore, the
capacity of the unit is limited to what the photovoltaic panels are providing:
If Smart Grid pulse meter is...
Available
Not available
The protective functions (water pipe freeze prevention, drain prevention, room
frost protection, tank disinfection) and defrost are NOT overruled (capacity will
not be limited for these functions)
Forced on:
Similar to Recommended on, but there is no capacity limitation. The goal is NOT to
use the grid as much as possible.
Emergency mode. In case emergency mode is active, buffering with electrical
heater is NOT possible in Forced on and Recommended on operation modes.
Power consumption control
See
"6  Application
guidelines"  [
functionality.
[9.8.5] Smart grid operation
2
0
Recommended on
1
Forced on
Then the limit is...
Decided by the unit based on the input
of the Smart Grid pulse meter.
Decided by [9.8.8] Limit setting
kW
4
  31] for detailed information about this
mode
EBLA09~16D + EDLA09~16D
Daikin Altherma 3 M
4P620241-1B – 2022.05